| General |
| Model | Wall surface mounted |
| Material | Plastic |
| Colour | RAL 9005 |
| Scope of delivery | Complete ready-to-install unit, including pleated filter |
| Fan | Diagonal, 1~ capacitor motor |
| Airflow free blowing (with pleated filter) | At 50 Hz: 625 m³/h, At 60 Hz: 716 m³/h |
| Airflow with associated exhaust filter including pleated filter | At 50 Hz: 565 m³/h, At 60 Hz: 645 m³/h |
| Airflow free-blowing (with filter) | At 50 Hz: 540 m³/h, At 60 Hz: 590 m³/h |
| Airflow with associated exhaust filter including felt filter | At 50 Hz: 444 m³/h, At 60 Hz: 498 m³/h |
| Rated operating voltage | 115 V, 1~, 50 Hz/60 Hz |
| Rated power Pel | At 50 Hz: 78.7 W, At 60 Hz: 102.8 W |
| Rated current max. | At 50 Hz: 0.81 A, At 60 Hz: 0.9 A |
| Width | 323 mm |
| Height | 323 mm |
| Depth | 144,5 mm |
| Built-in depth | 124 mm |
| Mounting cutout | Cutout width: 292 mm, Cutout height: 292 mm |
| Degree of protection IP according to IEC 60 529 | IP 54 with nonwoven filter/pleated filter, IP 55 with pleated filter and absorber mat, IP 56 with nonwoven filter/pleated filter and spray water hood |
| NEMA degree of protection | Type 12 with felt filter/pleated filter, Type 3, 3R, 4, 4X with felt filter/pleated filter and spray water hood |
| Fuse | Circuit breaker/fuse: 6 A |
| Note | For the filter fan 3237.XXX, the electrical connection is made via 2 individual wires (approx. 300 mm length) on the device; for all other filter fans, via spring clamp terminal. |
| Operating temperature range | -30 °C...55 °C |
| Storage temperature range | -30 °C...70 °C |
| Sound pressure level | At 50 Hz: 62 dB(A), At 60 Hz: 65 dB(A) |
The Rittal SK 3243.718 is a
filter fan of the SK Blue e+ series, designed for
enclosure climate control in industrial applications. It serves for controlled ventilation of enclosures, regulating internal temperature and extending the service life of installed electronic components. The unit is designed for
wall mounting and is installed tool-free, accelerating installation on enclosure surfaces. The housing is made of
plastic and is finished in
RAL 9005 (black), enabling visual integration into standardized enclosure environments.
Applications
The filter fan is intended for use in industrial environments where continuous ventilation is required to ensure heat dissipation and protection against dust and fine dirt. It is particularly suitable for enclosures in production plants, automation systems, or machine controls, where constant air circulation is necessary. The integrated filter technology ensures that incoming air is cleaned, maintaining the internal hygiene of the enclosure.
Functions and Equipment in Detail
The fan features a
diagonal fan with a 1~ capacitor motor, ensuring more uniform and consistent airflow within the enclosure. The diagonal discharge direction provides better air distribution, leading to more even cooling of electronic components. The delivery includes a
pleated filter, already mounted in the device, enabling a maximum free airflow of 625 m³/h at 50 Hz or 716 m³/h at 60 Hz. Airflow reduces to 565 m³/h (50 Hz) or 645 m³/h (60 Hz) when an outlet filter is used. Alternatively, a non-woven filter can be used, with free airflow at 540 m³/h (50 Hz) or 590 m³/h (60 Hz).
Technology Explained Simply
The
diagonal fan technology offers higher pressure stability compared to radial fans, which is particularly advantageous when facing resistance in the air path, such as filters or outlet openings. This ensures consistent airflow even under load conditions. The fan operates at a
rated supply voltage of 115 V, 1~, 50 Hz/60 Hz, making it suitable for many industrial power networks. The rated power is 78.7 W at 50 Hz and 102.8 W at 60 Hz, with a maximum rated current of 0.81 A (50 Hz) or 0.9 A (60 Hz). The unit is equipped with a
6 A fuse for operational protection.
Compatibility and Accessories
The filter fan can be combined with various accessories to increase protection ratings. Protection class IP 55 can be achieved when using a pleated filter together with an absorber mat. With a spray water hood and a non-woven/pleated filter, protection class IP 56 is possible. Correspondingly, NEMA protection classes Type 12 (with non-woven/pleated filter) or Type 3, 3R, 4, 4X (with non-woven/pleated filter and spray water hood) can be realized. Compatible accessories include outlet filters, replacement filter mats, speed controllers, digital temperature display and control, and a blanking plate for the mounting cutout.
Mounting and Installation
Mounting is tool-free onto the enclosure wall. The mounting cutout measures 292 mm in width and height, with an installation depth of 124 mm. The unit dimensions are 323 mm (width) × 323 mm (height) × 144.5 mm (depth). Electrical connection is made via two individual conductors (approx. 300 mm length) on the device, as is the case with models of the 3237 series. Mounting is accelerated by optimized latching hooks, and filter replacement is simplified thanks to a new opening mechanism on the louver grille.
Operational Advantages
The operating temperature range is between -30 °C and +55 °C, enabling use in environments with varying climatic conditions. Storage temperature can reach up to +70 °C. The sound pressure level is 62 dB(A) at 50 Hz and 65 dB(A) at 60 Hz, representing acceptable noise emissions for industrial applications. The combination of tool-free mounting, integrated filter, and high airflow makes the SK 3243.718 a reliable solution for enclosure climate control.
Protection Class and Environmental Conditions
Standard protection class is IP 54 with non-woven or pleated filter. Higher protection classes can be achieved with additional components such as absorber mats or spray water hoods, enabling use in humid or dusty environments. IP 56 protection guards against splashing water and dust, which is relevant for outdoor areas or production halls with high contamination risk.
Operational Safety and Connection
The fan is designed for operation in a temperature range of -30 °C to +55 °C. Electrical connection is via two individual conductors on the device, as is the case with the 3237.XXX model series. The 6 A fuse protects against overloads. The unit is designed for use in industrial facilities where continuous and reliable ventilation is required.