| General |
| Model | Wall surface mounted |
| Material | Plastic |
| Colour | RAL 9005 |
| Scope of delivery | Complete ready-to-install unit, including pleated filter |
| Fan | Diagonal, 1~ capacitor motor |
| Airflow free blowing (with pleated filter) | At 50 Hz: 625 m³/h, At 60 Hz: 716 m³/h |
| Airflow with associated exhaust filter including pleated filter | At 50 Hz: 565 m³/h, At 60 Hz: 645 m³/h |
| Airflow free-blowing (with filter) | At 50 Hz: 540 m³/h, At 60 Hz: 590 m³/h |
| Airflow with associated exhaust filter including felt filter | At 50 Hz: 444 m³/h, At 60 Hz: 498 m³/h |
| Rated operating voltage | 230 V, 1~, 50 Hz/60 Hz |
| Rated power Pel | At 50 Hz: 77.7 W, At 60 Hz: 106.4 W |
| Rated current max. | At 50 Hz: 0.39 A, At 60 Hz: 0.47 A |
| Width | 323 mm |
| Height | 323 mm |
| Depth | 144,5 mm |
| Built-in depth | 124 mm |
| Mounting cutout | Cutout width: 292 mm, Cutout height: 292 mm |
| Degree of protection IP according to IEC 60 529 | IP 54 with nonwoven filter/pleated filter, IP 55 with pleated filter and absorber mat, IP 56 with nonwoven filter/pleated filter and spray water hood |
| NEMA degree of protection | Type 12 with felt filter/pleated filter, Type 3, 3R, 4, 4X with felt filter/pleated filter and spray water hood |
| Fuse | Circuit breaker/fuse: 4 A |
| Note | For the filter fan 3237.XXX, the electrical connection is made via 2 individual wires (approx. 300 mm length) on the device; for all other filter fans, via spring clamp terminal. |
| Operating temperature range | -30 °C...55 °C |
| Storage temperature range | -30 °C...70 °C |
| Sound pressure level | At 50 Hz: 62 dB(A), At 60 Hz: 65 dB(A) |
The Rittal SK 3243.708 is a
filter fan of the SK Blue e+ series, designed for
enclosure climate control in industrial applications. It serves for controlled ventilation of enclosures, regulating internal temperature and extending the service life of installed electronic components. The unit is designed for
wall mounting and consists of a
plastic housing in the color
RAL 9005.
Applications
The filter fan is suitable for use in industrial environments where continuous and reliable ventilation of enclosures is required. It is commonly used in machine building, automation technology, power supply systems, and other areas where electronic devices must be protected from overheating. The
protection rating IP 54 (with nonwoven or pleated filter) ensures protection against dust and splashing water, allowing the fan to operate even in slightly contaminated or humid environments. With additional components such as an absorber mat or spray water hood, the protection rating can be increased to IP 55 or IP 56, enabling use in more demanding environments. The corresponding
NEMA protection ratings (Type 12, 3, 3R, 4, 4X) highlight its suitability for industrial applications in various regions.
Functions and Equipment in Detail
The fan features
diagonal fan technology with a
1~ capacitor motor, providing higher pressure stability. This ensures more uniform and consistent air circulation within the enclosure, improving cooling performance and reducing stress on electronic components. The diagonal airflow direction also ensures more even cooling of the enclosure interior. Airflow performance is
625 m³/h at 50 Hz and
716 m³/h at 60 Hz in free-blow operation with a pleated filter. When using an outlet filter, performance drops to 565 m³/h (50 Hz) or 645 m³/h (60 Hz). The
rated power is 77.7 W (50 Hz) or 106.4 W (60 Hz), and the
rated current is up to 0.39 A (50 Hz) or 0.47 A (60 Hz). The
operating temperature ranges from -30 °C to +55 °C, enabling use in regions with varying climates.
Technology Explained Simply
The
diagonal fan technology ensures that air flows out of the device diagonally rather than vertically. This prevents pressure loss and ensures more even air distribution within the enclosure. The
pleated filters included in the delivery filter particles from incoming air, increasing air purity inside the enclosure.
Tool-free mounting is achieved via optimized latching hooks, allowing quick and secure attachment to the enclosure. Electrical connection is made via
2 individual conductors (approx. 300 mm length) on the device, typical for the 3237.XXX series. The
sound pressure level is 62 dB(A) (50 Hz) and 65 dB(A) (60 Hz), representing acceptable noise emissions for industrial applications.
Compatibility and Accessories
The filter fan can be combined with various accessories to extend protection rating or functionality. These include
outlet filters in RAL 9005,
absorber mats for IP 55,
spray water hoods for IP 56, and
nonwoven filters as an alternative to pleated filters. For precise temperature control,
thermostats or
digital temperature display and control units can be used. A
speed controller allows adjustment of airflow according to operating conditions. Replacement filter mats are available in packs of 5 or 50. A
blanking plate is also available to close mounting cutouts.
Mounting and Installation
Mounting is tool-free on a flat surface, requiring a mounting cutout of 292 mm width and 292 mm height. The installation depth is 124 mm, and the overall dimensions of the device are 323 mm (width) × 323 mm (height) × 144.5 mm (depth). The unit is designed for a nominal voltage of
230 V, 1~, 50 Hz/60 Hz. The fuse must be rated with a
4 A circuit breaker/fuse. The unit is delivered fully assembled and ready for installation, including an integrated pleated filter.
Advantages in Operation
The SK 3243.708 offers high airflow performance with low energy consumption and enables easy maintenance via the new opening mechanism on the louver grille. Tool-free mounting and the high pressure stability of diagonal fan technology ensure quick installation and reliable cooling performance. Integrated filtration protects enclosure components from contamination. Compatibility with various accessories allows adaptation to specific requirements regarding protection rating, airflow, and temperature control.