| General |
| Model | Wall mounting, EMC |
| Material | Plastic |
| Colour | RAL 7035 |
| Scope of delivery | Complete ready-to-install unit, including EMI filter mat |
| Fan | Axial, split-pole motor |
| Airflow free-blowing (with filter) | At 50 Hz: 53 m³/h, At 60 Hz: 64 m³/h |
| Airflow with associated exhaust filter including felt filter | At 50 Hz: 40 m³/h, At 60 Hz: 46 m³/h |
| Rated operating voltage | 230 V, 1~, 50 Hz/60 Hz |
| Rated power Pel | At 50 Hz: 14.7 W, At 60 Hz: 16.5 W |
| Rated current max. | At 50 Hz: 0.1 A, At 60 Hz: 0.12 A |
| Width | 148,5 mm |
| Height | 148,5 mm |
| Depth | 82,5 mm |
| Built-in depth | 64 mm |
| Mounting cutout | Cutout width: 124 mm, cutout height: 124 mm |
| Degree of protection IP according to IEC 60 529 | IP 54 with felt filter, IP 56 with felt filter and spray hood |
| NEMA degree of protection | Type 12 with felt filter, Type 3, 3R, 4, 4X with felt filter and spray shield |
| Fuse | Circuit breaker/fuse: 2 A |
| Note | To improve energy efficiency and increase device lifespan, use of temperature controllers or indicators is recommended. |
| Operating temperature range | -15 °C...55 °C |
| Storage temperature range | -30 °C...70 °C |
| Sound pressure level | At 50 Hz: 52 dB(A), At 60 Hz: 54 dB(A) |
The Rittal SK 3238.800 is a
filter fan with
EMC shielding, designed for
enclosure climate control. It serves for controlled ventilation of enclosures to regulate internal temperature and ensure the functionality of installed electronic components. The unit is designed for
wall mounting and consists of
plastic in the colour
RAL 7035. It is compactly dimensioned with width, height and depth each measuring 148.5 mm, 148.5 mm and 82.5 mm, with an installation depth of 64 mm. The mounting cutout requires a 124 mm width and 124 mm height opening in the enclosure sheet metal.
Applications
The filter fan is intended for use in industrial environments where continuous and reliable ventilation is required. It is particularly suitable for enclosures in production plants, automation systems or building automation. The integrated
EMC shielding meets requirement level 2 according to EN 61587-3, ensuring high attenuation of electromagnetic interference. This protects sensitive electronic devices from disturbances caused by external electromagnetic fields.
Functions and Equipment in Detail
The fan features an
axial fan with split-pole motor, ensuring uniform and constant air circulation. The
diagonal fan technology increases pressure stability and ensures homogeneous ventilation of the enclosure. Air performance is 53 m³/h free blowing (with non-woven filter) at 50 Hz and 64 m³/h at 60 Hz. When using an additional outlet filter, air performance reduces to 40 m³/h (50 Hz) or 46 m³/h (60 Hz). The unit is tool-free to mount, with optimised latching hooks accelerating installation on the enclosure. A new opening mechanism on the louver grille enables easy filter replacement.
Technology Explained Simply
The operating voltage is 230 V, 1~, designed for frequencies of 50 Hz and 60 Hz. Rated power is 14.7 W (50 Hz) or 16.5 W (60 Hz), with maximum rated current at 0.1 A (50 Hz) or 0.12 A (60 Hz). The unit is equipped with a 2 A fuse for overload protection. The sound pressure level is 52 dB(A) at 50 Hz and 54 dB(A) at 60 Hz, enabling acoustically low-stress operation. Operating temperature ranges from -15 °C to 55 °C, with storage temperature from -30 °C to 70 °C.
Compatibility and Accessories
The fan is supplied with a
non-woven filter, included in the delivery scope. The protection rating is
IP 54 with non-woven filter and
IP 56 when using a spray hood. According to NEMA standards, the unit corresponds to
Type 12 with non-woven filter and
Type 3, 3R, 4, 4X with non-woven filter and spray hood. Suitable accessories include a
Blue e+ outlet filter EMC, a
spray hood, a
thermostat, a
speed controller, a
digital temperature display, and a
hygrostat. These components can be used to improve energy efficiency and extend the service life of the device.
Mounting and Installation
Mounting is tool-free on the enclosure wall. The unit is inserted into the designated mounting cutout (124 mm × 124 mm) and secured using latching hooks. The installation depth of 64 mm must be considered in the enclosure. The EMC filter mat is already integrated, so no additional measures for electromagnetic shielding are required.
Operational Advantages
The filter fan provides a reliable and maintenance-friendly ventilation solution. The integrated EMC shielding protects sensitive devices from interference. Tool-free mounting and easy filter replacement reduce maintenance time. The high pressure stability of the diagonal fan technology ensures even air distribution within the enclosure. The recommendation to use temperature controllers or displays serves to optimise energy consumption and extend the device’s service life.