| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Stainless steel 1.4301 (AISI 304) |
| Colour | RAL 9007 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 4 kW, Cooling capacity L35 L35/60 Hz: 4 kW, Cooling capacity L35 L50/50 Hz: 3.02 kW, Cooling capacity L35 L50/60 Hz: 3.02 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V), full installation not possible |
| Rated power | 1,45 kW |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling capacity factor L35 L35 (EER) 50 Hz: 3.08, Cooling capacity factor L35 L35 (EER) 60 Hz: 3.08 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 6,5 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 393 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-513A, quantity: 1.8 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 1.14 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 1.3 kW, Rated power L35 L35/60 Hz: 1.3 kW, Rated power L35 L50/50 Hz: 1.28 kW, Rated power L35 L50/60 Hz: 1.28 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 1.241,56 |
The Rittal SK 3188640 is a wall-mounted cooling unit of the Blue e+ series, designed for climate control of enclosures in semi-outdoor environments. It features a total cooling capacity of 4.0 kW at an operating voltage of 380 V to 480 V, 3~, 50 Hz/60 Hz. The unit is made of stainless steel 1.4301 (AISI 304) and finished in RAL 9007, ensuring high corrosion resistance and a robust surface for industrial applications. Dimensions are 450 mm (width) × 1,600 mm (height) × 393 mm (depth), requiring a mounting cutout of 433 mm (width) × 1,579 mm (height). The cooling unit is not suitable for full enclosure installation.
Applications
This unit is designed for use in industrial environments, particularly in enclosures installed in semi-outdoor areas. Operating temperature ranges are between -20 °C and 60 °C, with the refrigerant circuit operating actively between 3 °C and 60 °C and the Heat Pipe operating between -20 °C and 45 °C. Storage temperature ranges extend from -40 °C to 70 °C. Temperature control is managed by an e+ controller, factory-set to +35 °C, with an adjustable range of 20 °C to 50 °C.
Functions and Equipment in Detail
The cooling unit features a condenser with hydrophobic RiNano coating, which reduces condensation formation and simplifies maintenance. The integrated electric condensate evaporation system ensures that condensate is evaporated directly within the unit, eliminating the need for an external drain. The unit is pre-wired with a plug-in terminal strip and includes mounting hardware. Airflow performance is 2,300 m³/h for both the outdoor and indoor circuits. Rated power is 1.45 kW.
Technology Explained Simply
Cooling capacity is measured according to DIN EN 14511. At an outdoor temperature of 35 °C (L35) and an indoor temperature of 35 °C (L35), the cooling capacity is 4.0 kW at 50 Hz and 60 Hz. At an indoor temperature of 50 °C (L50), the cooling capacity is 3.02 kW. Energy efficiency is characterized by an Energy efficiency ratio (EER) of 3.08 (at 50 Hz and 60 Hz) and a Seasonal energy efficiency ratio (SEER) of 6.5. Variable-speed components and Heat Pipe technology provide an average energy saving of 75 % compared to conventional systems. The refrigerant R-513A is used in a quantity of 1.8 kg, with a Global Warming Potential (GWP) of 631 and a CO₂ equivalent of 1.14 t. The permissible operating pressure is 24 bar.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ units, the IoT Interface with article number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages. Available accessories include the SK condensate hose 12 x 2 mm (length 10 m), cover for the connection box (article number 3355.210), metal filters and filter mats for the specified SK models, and an air deflector for SK 3188.xxx/3189.xxx.
Installation and Mounting
The unit is designed for wall mounting. Required mounting cutouts are 433 mm (width) and 1,579 mm (height). Installation requires a suitable electrical supply in the range of 380 V to 480 V, 3~, 50 Hz/60 Hz, with a tolerance of -10 % (342 V) to +6 % (509 V). Surge protection is required: for operating voltage below 460 V (3~) with Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltage above 460 V (3~) with Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
Component-friendly cooling extends the service life of components within the enclosure and the cooling unit itself. Intuitive operation is provided via a touch display and intelligent interfaces. Multi-voltage capability enables worldwide use. Integrated condensate evaporation reduces maintenance effort, as no external drain is required. Energy efficiency is supported by variable-speed components and Heat Pipe technology, resulting in an average energy saving of 75 %. Protection class IP 55 (indoor circuit) and UL Type 12 as well as UL Type 3R (NEMA) ensure a high level of protection against dust and splashing water, suitable for semi-outdoor use.
Protection Class and Operating Environment
The unit is designed for use in semi-outdoor environments. Protection class IP 55 (indoor circuit) according to EN 60 529 and NEMA protection classes UL Type 12 and UL Type 3R provide protection against dust and splashing water. Operating temperature ranges are between -20 °C and 60 °C, with the Heat Pipe operating up to 45 °C. Storage temperature ranges extend from -40 °C to 70 °C. Operating voltage is 380 V to 480 V, 3~, 50 Hz/60 Hz, with a tolerance of -10 % to +6 %.