| General |
| Model | Wall mounting, Outdoor |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Aluminium AlMg3 |
| Surface protection | Powder-coated, UV-resistant pure polyester |
| Colour | RAL 7035 |
| Scope of delivery | Refrigerant with hydrophobic RiNano coating, integrated electric condensate evaporation, pre-wired (pluggable terminal block), mounting frame for universal attachment to outdoor enclosures for surface mounting, panel mounting and flush mounting, incl. mounting material |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 3.7 kW, Cooling capacity L35 L35/60 Hz: 3.7 kW, Cooling capacity L35 L50/50 Hz: 2.66 kW, Cooling capacity L35 L50/60 Hz: 2.66 kW |
| Rated operating voltage | 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the partner and Rittal for the free use of the software according to these license terms. For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 1,57 kW |
| Rated power Pel | Rated power L35 L35/50 Hz: 1.55 kW, Rated power L35 L35/60 Hz: 1.55 kW, Rated power L35 L50/50 Hz: 1.57 kW, Rated power L35 L50/60 Hz: 1.57 kW |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Width | 465 mm |
| Height | 1.640 mm |
| Depth | 360 mm |
| Device dimensions including gasket frame and design hood | Width: 517 mm, Height: 1,692 mm, Depth: 360 mm |
| Mounting type | Universal installation (surface mounting, partial installation, full installation) |
| Degree of protection IP according to IEC 60 529 | With mounting frame: internal circuit IP 56, without mounting frame: internal circuit IP 54 |
| NEMA degree of protection | with mounting frame: UL Type 12/3R/4, without mounting frame: UL Type 12/3R |
| Air performance (free blowing) | External circuit: 2,300 m³/h, Internal circuit: 2,300 m³/h |
| Refrigerant/cooling medium | Refrigerant: R-513A, quantity: 1.8 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 1.14 t |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance coefficient L35 L35 (EER) 50 Hz: 2.39, Cooling performance coefficient L35 L35 (EER) 60 Hz: 2.39 |
| Suitable for | Housing type: Toptec, width: ≥ 800 mm, height: ≥ 1,800 mm |
| Suitable for part no. | 9782.828, 9783.888 |
| Adjustment range | 20 °C...50 °C |
| Operating temperature range | -30 °C...60 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -30 °C...45 °C |
| Storage temperature range | -40 °C...70 °C |
| Permissible operating pressure (p max.) | 2.4 MPa |
| Sound pressure level | 71 dB(A) |
| PCF/VE (Cradle-to-Gate) | 1.340,61 |
The Rittal SK 3188340 is a wall-mounted cooling unit of the Blue e+ series, designed for outdoor use. It is intended for climate control of enclosures and industrial housings, particularly in demanding environments with high temperature loads or humid air. The unit is designed for mounting on Toptec housings with a minimum width of 800 mm and a minimum height of 1,800 mm, and is suitable for surface mounting, partial installation, and full installation. The unit is made of aluminium AlMg3 with a powder-coated, UV-resistant surface in RAL 7035, ensuring high corrosion and weather resistance.
Applications
This cooling unit is intended for industrial applications outdoors, where a constant internal temperature in the enclosure is required. It is suitable for locations with ambient temperatures between -30 °C and 60 °C. The protection rating IP 56 (with mounting frame) or IP 54 (without mounting frame) according to IEC 60 529, as well as the NEMA protection rating UL Type 12/3R/4 (with mounting frame) or UL Type 12/3R (without mounting frame), protects the unit against dust, splashing water, and other environmental influences. The operating temperature of the refrigerant circuit ranges from 3 °C to 60 °C, while Heat Pipe operation is permitted up to 45 °C.
Functions and Equipment in Detail
The unit features an integrated e+ controller, factory-set to an internal temperature of +35 °C. The adjustable range is 20 °C to 50 °C, allowing temperature adjustment according to requirements. The cooling capacity is 3.7 kW at L35 operation (50 Hz and 60 Hz) and 2.66 kW at L50 operation (50 Hz and 60 Hz), measured according to DIN EN 14511. The rated power is 1.57 kW, with the nominal power varying between 1.55 kW and 1.57 kW depending on operating conditions. Energy efficiency is achieved with a coefficient of performance (EER) of 2.39 at 50 Hz and 60 Hz L35 operation.
Technology Explained Simply
The cooling unit uses refrigerant R-513A with a quantity of 1.8 kg. The Global Warming Potential (GWP) is 631, equivalent to 1.14 t of CO₂. The integrated electric condensate evaporation system ensures that condensate is automatically evaporated, eliminating the need for drainage. The condenser is coated with a hydrophobic RiNano coating, improving drip performance. The air flow rate is 2,300 m³/h for both the external and internal circuits, ensuring efficient air circulation within the enclosure. The sound pressure level is 71 dB(A), which is acceptable for industrial applications.
Compatibility and Accessories
The unit is compatible with Toptec housings and fits article numbers 9782.828 and 9783.888. Accessories include, among others, a thermostat for internal temperature control, a condensate hose (12 x 2 mm, length 10 m), a cover for the connection box (article number 3355.210), a hygrostat, a door position switch, a temperature sensor for Blue e+ cooling units, and an IoT interface (article number 3124.300). The IoT interface enables remote monitoring and networking of the cooling unit, allowing device data, statuses, and system messages to be monitored.
Mounting and Installation
The cooling unit is supplied with a mounting frame that enables universal fastening to outdoor housings. Installation can be done in surface, partial, or full installation variants. The unit dimensions are 465 mm (width) × 1,640 mm (height) × 360 mm (depth). Including the sealing frame and design hood, the total width is 517 mm and the total height is 1,692 mm. The unit is pre-wired with a plug-in terminal strip and supplied with fastening materials. The rated operating voltage is 380 V to 480 V, 3~, 50 Hz/60 Hz, with a tolerance of -10 % (342 V) at 380 V and +6 % (509 V) at 480 V. For protection of the unit, appropriate surge protection is required: for operating voltages below 460 V (3~), Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV; for operating voltages above 460 V (3~), Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV.
Operational Advantages
Thanks to speed-controlled components and Heat Pipe technology, an average energy saving of 75 % is achieved. The component-friendly cooling extends the service life of components in the enclosure and the cooling unit itself. Intuitive operation is provided via a touch display and intelligent interfaces. The integrated condensate evaporation reduces maintenance effort, as no drainage is required. The high protection rating and wide operating temperature range make the unit suitable for demanding industrial environments.
Scope of Delivery
The unit is supplied with a condenser (hydrophobic RiNano coating), integrated electric condensate evaporation, pre-connected plug-in terminal strip, mounting frame for universal fastening to outdoor housings (for surface, partial, and full installation), and fastening materials.