| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | steel sheet |
| Colour | RAL 7035 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 2 kW, Cooling capacity L35 L35/60 Hz: 2 kW, Cooling capacity L35 L50/50 Hz: 1.29 kW, Cooling capacity L35 L50/60 Hz: 1.29 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,73 kW |
| Air performance (free blowing) | External circuit: 1,250 m³/h, internal circuit: 1,250 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 3.23, Cooling performance factor L35 L35 (EER) 60 Hz: 3.23 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 7,6 |
| Width | 450 mm |
| Height | 1.600 mm |
| Depth | 294 mm |
| Required mounting cutout | Cutout width: 433 mm, cutout height: 1,579 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-513A, Quantity: 1.07 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 0.68 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.62 kW, rated power L35 L35/60 Hz: 0.62 kW, rated power L35 L50/50 Hz: 0.6 kW, rated power L35 L50/60 Hz: 0.6 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 896,57 |
Benefits: 75% energy saved due to speed-regulated components and heat pipe technology
Suitable for international use due to a unique multi-voltage capability
Longer service life of the components inside the enclosure and the cooling unit due to component-friendly cooling
Intuitive operation due to touch display and intelligent interfaces
Material: Sheet steel
Colour: RAL 7035
Protection category IP to IEC 60 529: Internal circuit IP 55
Supply includes: Assembly parts
Packs of: 1 pc(s).
EAN: 4028177709584
Customs tariff number: 84158200
eCl@ss 5.1: 27180704
eCl@ss 7.0: 27180704
ETIM 6.0: EC000855
Total cooling output to DIN EN 14511: L 35 L 35 at 50 Hz: 2 kW
L 35 L 35 at 60 Hz: 2 kW
L 35 L 50 at 50 Hz: 1.29 kW
L 35 L 50 at 60 Hz: 1.29 kW
Air throughput (unimpeded air flow): External circuit: 1250 m³/h
Internal circuit: 1250 m³/h
Rated operating voltage: 110 V - 240 V, 1~, 50 Hz/60 Hz
380 V - 480 V, 3~, 50 Hz/60 Hz
Dimensions: Width: 450 mm
Height: 1600 mm
Depth: 294 mm
Temperature control: e+ controller (factory setting +35°C)
Temperature range: Bearing: -40°C...+70°C
Operation (environment): -20°C...+60°C
Setting range: +20°C...+50°C
Refrigerant/cooling medium: Refrigerant: R134a
Quantity: 1150 g
Power consumption Pel: L 35 L 35 at 50 Hz: 0.57 kW
L 35 L 35 at 60 Hz: 0.57 kW
L 35 L 50 at 50 Hz: 0.6 kW
L 35 L 50 at 60 Hz: 0.6 kW
Rated output: 0.73 kW
Energy efficiency ratio (EER) 50 Hz L35 L35 to DIN EN 14511: 3.5
8.1