| General |
| Model | Wall surface mounted |
| Market-relevant product changes | The cover for the connection box to protect the electrical connection on the cooling unit is no longer included in the scope of delivery from the beginning of 2024. The covers 3355.200 and 3355.210 can be ordered optionally as accessories. |
| Material | Stainless steel 1.4301 (AISI 304) |
| Colour | RAL 9007 |
| Scope of delivery | Condensate trap with hydrophobic RiNano coating, Integrated electric condensate evaporation, Including mounting material, Pre-wired for connection (pluggable terminal block) |
| Options | For remote monitoring and networking of cooling units and chillers from the Blue e+ generation, use the IoT interface with article number 3124.300. Increase machine availability and process safety by remotely monitoring device data, statuses and system messages. |
| Total cooling capacity according to DIN EN 14511 | Cooling capacity L35 L35/50 Hz: 1.6 kW, cooling capacity L35 L35/60 Hz: 1.6 kW, cooling capacity L35 L50/50 Hz: 1.2 kW, cooling capacity L35 L50/60 Hz: 1.2 kW |
| Rated operating voltage | 110 V - 240 V, 1~, 50 Hz/60 Hz, 380 V - 480 V, 3~, 50 Hz/60 Hz |
| Note | By downloading the software, a contract is established between the contracting party and Rittal for the free use of the software according to these license terms. Only suitable for semi-outdoor use (see instruction manual). For protection of Blue e+ cooling units, appropriate surge protection must be provided: - Operating voltage < 460 V (3~): Uc 275 V, Imax 40 kA, In 20 kA, Up 1.5 kV. - Operating voltage > 460 V (3~): Uc 385 V, Imax 40 kA, In 20 kA, Up 1.5 kV. |
| Note on part number | Tolerance: 110 V -10 % (99 V) and 240 V +10 % (264 V) / 380 V -10 % (342 V) and 480 V +6 % (509 V) |
| Rated power | 0,7 kW |
| Air performance (free blowing) | External circuit: 895 m³/h, Internal circuit: 700 m³/h |
| Energy efficiency ratio (EER) 50/60 Hz L35 L35 | Cooling performance factor L35 L35 (EER) 50 Hz: 2.96, Cooling performance factor L35 L35 (EER) 60 Hz: 2.96 |
| Seasonal energy efficiency ratio (SEER) 50/60 Hz | 5,5 |
| Width | 400 mm |
| Height | 950 mm |
| Depth | 310 mm |
| Required mounting cutout | Cutout width: 383 mm, cutout height: 929 mm |
| Degree of protection IP according to EN 60 529 | Internal circuit IP 55 |
| NEMA degree of protection | UL Type 12, UL Type 3R |
| Refrigerant/cooling medium | Refrigerant: R-513A, quantity: 0.76 kg, Global Warming Potential (GWP): 631, CO₂ equivalent (CO₂e): 0.48 t |
| Temperature control | e+ Controller (factory setting +35 °C) |
| Operating temperature range | -20 °C...60 °C |
| Storage temperature range | -40 °C...70 °C |
| Operating temperature range refrigerant circuit (active) | 3 °C...60 °C |
| Operating temperature range heat pipe | -20 °C...45 °C |
| Adjustment range | 20 °C...50 °C |
| Rated power Pel | Rated power L35 L35/50 Hz: 0.54 kW, rated power L35 L35/60 Hz: 0.54 kW, rated power L35 L50/50 Hz: 0.61 kW, rated power L35 L50/60 Hz: 0.61 kW |
| Permissible operating pressure (p max.) | 24 bar |
| PCF/VE (Cradle-to-Gate) | 660,04 |
The Rittal SK 3185530 is a wall-mounted cooling unit of the Blue e+ series, specifically designed for climate control of enclosures in semi-outdoor environments. It features a total cooling capacity of 1.6 kW at an operating voltage of 110 V to 240 V (1~, 50/60 Hz) or 380 V to 480 V (3~, 50/60 Hz). The unit is made of stainless steel 1.4301 (AISI 304) and finished in RAL 9007, ensuring high corrosion resistance and long service life. Dimensions are 400 mm (width) × 950 mm (height) × 310 mm (depth), requiring a mounting cutout of 383 mm (width) × 929 mm (height). The cooling unit is pre-wired and includes a plug-in terminal strip and mounting hardware. The condenser is coated with a hydrophobic RiNano coating, and an integrated electric condensate evaporation system ensures efficient dehumidification. Temperature control is managed by an e+ controller, factory-set to +35 °C, with an adjustable range from 20 °C to 50 °C.
Applications
This cooling unit is intended for use in semi-outdoor environments, allowing installation in protected outdoor areas or rooms with increased environmental stress. It is suitable for industrial applications where a constant internal temperature in the enclosure is required to ensure the proper function of electronic components. The operating temperature of the unit ranges from -20 °C to 60 °C, with the refrigerant circuit active between 3 °C and 60 °C. The Heat Pipe technology provides gentle component cooling, extending the service life of components installed in the enclosure.
Functions and Equipment in Detail
The unit operates with refrigerant R-513A, which has a Global Warming Potential (GWP) of 631 and a system charge of 0.76 kg. Airflow is 895 m³/h in the external circuit and 700 m³/h in the internal circuit. Energy efficiency is enhanced by variable-speed components and Heat Pipe technology, achieving an average energy saving of 75 %. The coefficient of performance (EER) is 2.96 at 50 Hz and 60 Hz in L35-L35 operation, while the Seasonal Energy Efficiency Ratio (SEER) is 5.5. The rated power is 0.7 kW, with nominal power varying between 0.54 kW and 0.61 kW depending on operating conditions.
Technology Explained Simply
The Heat Pipe technology enables efficient heat dissipation by transferring heat from the internal to the external circuit without requiring additional mechanical components. Variable-speed components adjust their performance to match current cooling demand, reducing energy consumption. The integrated electric condensate evaporation system ensures that condensate is evaporated directly within the unit, eliminating the need for an external drain. The hydrophobic RiNano coating on the condenser prevents condensate formation on the surface, reducing maintenance requirements.
Compatibility and Accessories
For remote monitoring and networking of Blue e+ cooling units, the IoT Interface with part number 3124.300 can be used. This enables monitoring of device data, statuses, and system messages to increase machine availability and process safety. Available accessories include covers for the connection box (part numbers 3355.200 and 3355.210), a condensate hose (12 x 2 mm, length 10 m), an air deflector for SK 3185.xxx, a temperature sensor for Blue e+ cooling units, and metal and filter mats for SK 3185830.
Installation and Mounting
The unit is designed for wall mounting and requires a mounting cutout of 383 mm (width) × 929 mm (height). Mounting is done using the included hardware. The pre-wired connection with a plug-in terminal strip simplifies installation. The internal circuit has an IP 55 protection rating according to EN 60 529, meaning it is dust-tight and protected against splashing water. The NEMA protection rating corresponds to UL Type 12 and UL Type 3R, providing protection against dust, splashing water, and light splashing water in outdoor applications. For operation, appropriate surge protection must be provided: for operating voltages below 460 V (3~), surge protection with Uc 275 V, Imax 40 kA, In 20 kA, and Up 1.5 kV is required; for voltages above 460 V (3~), Uc 385 V, Imax 40 kA, In 20 kA, and Up 1.5 kV applies.
Operational Advantages
The cooling unit offers high energy efficiency through variable-speed components and Heat Pipe technology, reducing energy consumption. The integrated condensate evaporation and hydrophobic coating minimize maintenance effort. Multi-voltage capability enables worldwide use. Remote monitoring via the IoT Interface enhances process safety. The robust stainless steel construction ensures long service life and high corrosion resistance. The operating temperature range and protection ratings make the unit suitable for a wide range of industrial applications, especially in semi-outdoor environments.
Protection Rating and Operating Conditions
The IP 55 protection rating for the internal circuit means the unit is dust-tight and protected against splashing water, suitable for industrial environments. The NEMA UL Type 12 and UL Type 3R ratings cover indoor use and protected outdoor applications. The unit's operating temperature range is -20 °C to 60 °C, with the refrigerant circuit active from 3 °C to 60 °C. The Heat Pipe can operate between -20 °C and 45 °C. The storage temperature range is -40 °C to 70 °C. The permissible operating pressure is 24 bar.
Energy Efficiency and Environment
The unit achieves an average energy saving of 75 % through variable-speed components and Heat Pipe technology. The coefficient of performance (EER) is 2.96, and the SEER value is 5.5, indicating high energy efficiency over the entire operating cycle. The refrigerant R-513A has a GWP of 631, representing a reduction in greenhouse gas emissions compared to older refrigerants. The CO₂ equivalent is 0.48 t. The PCF/VE (Cradle-to-Gate) is 660.04, accounting for environmental impact from raw material extraction to manufacturing.