| General |
| Product type | Relay card for speaker lines |
| Compatibility | RSC-132A monitoring unit |
| Connection capacity | 8 speaker circuits per card |
| Max. expansion | 4 cards per RSC-132A (32 circuits total) |
| Protection function | Relay disconnects affected line from 100V output in case of short circuit |
| Application | ELA/voice alarm systems with line monitoring |
| Built-in | 19" or system rack (depending on RSC housing) |
| Scope of delivery | 1x relay card for 8 speaker lines, 1x connection documentation / Quick Start Guide |
The relay card RSC-008A from RCS Audio-Systems is a modular component for integrating loudspeaker lines into
ELA systems (Electronic Loudspeaker Systems). It is specifically designed for use with the monitoring controller RSC-132A and enables the connection of up to
8 loudspeaker circuits per card. With the possibility of installing up to 4 cards per controller, the entire system can be expanded to up to 32 monitored loudspeaker lines. This configuration is particularly suitable for medium to large installations in safety-critical areas such as public buildings, transport facilities, or industrial complexes, where reliable voice alarm systems are required.
Applications
The card is used in
voice alarm systems designed in accordance with the standard
EN 54-16 for line monitoring. This standard specifies requirements for the reliability and functionality of alarm systems, particularly regarding the monitoring of loudspeaker lines. The RSC-008A supports these requirements through an integrated protection function that selectively disconnects the affected line in case of faults, without impacting the entire system.
Functions and Equipment in Detail
A central feature of the relay card is the
protection relay per loudspeaker line. In the event of a short circuit, the affected line is automatically disconnected from the 100V output of the amplifier after a measurement phase. This prevents damage to the amplifier and ensures that the remaining loudspeaker circuits continue to function. This function significantly increases the
operational safety of the entire system, as faults are localized and contained.
Technology Explained Simply
The card operates in conjunction with the RSC-132A controller, which handles line monitoring and control. The relay card itself performs the physical disconnection of loudspeaker lines in case of faults. The 100V technology used here is a standard solution in professional sound systems, as it enables high power density over long distances. The automatic shutdown occurs after a measurement phase to avoid false alarms caused by brief disturbances.
Compatibility and Accessories
The relay card is exclusively intended for use with the
RSC-132A monitoring controller. The maximum expansion is 4 cards per controller, enabling a total of 32 monitored loudspeaker circuits. The card is designed for installation in
48,3 cm ( 19 inch ) racks or system racks, with the exact mounting configuration depending on the respective RSC enclosure.
Mounting and Installation
Installation is carried out as part of the overall RSC-132A system. The card is inserted into the controller's enclosure and connected to the loudspeaker lines via designated connectors. The connection documentation included in the delivery supports correct wiring and configuration. Mounting requires no special tools or additional components.
Operational Advantages
Through selective disconnection of faulty loudspeaker lines, the functionality of the entire system is preserved. This is particularly important in safety-critical applications, where a complete failure of the alarm system must be avoided. The modular expandability allows for step-by-step system expansion without requiring modifications to the existing infrastructure. The card thus supports a flexible and scalable system architecture.
Scope of Delivery
The scope of delivery includes 1x relay card for 8 loudspeaker lines and 1x connection documentation / Quick Start Guide.