| Technical data |
| Dimensions (W x H x D) | 125 x 125 x 34 mm |
| Operation temperature | -20 to +60 °C |
| Contacts | 1 x changeover contact 48 VAC/DC 1 A |
| Degree of protection | IP43 (according to DIN EN 60 529) |
| Housing | Aluminium die-cast |
The blue manual call point HMH-001B from RCS Audio-Systems is a manual activation system for electroacoustic emergency warning systems (ELA) and is specifically designed for activating building alarms. The device is housed in a robust aluminium die-cast housing, which offers advantages over conventional plastic housings in terms of durability and weather resistance. The housing is UV-resistant, impact-resistant, and dimensionally stable, making it suitable for permanent use in indoor environments as well as in sheltered outdoor areas. The housing colour corresponds to RAL 5015, a standardised blue shade commonly used in safety applications.
Applications
The manual call point is primarily designed for manual activation of building alarms, particularly in installations without fire department connection. It serves as a physical activation mechanism directly connected to the trigger contacts of an ELA system. The clear labelling “Hausalarm” – which is replaceable – clearly indicates the function and supports rapid identification in an emergency. The device is used in buildings where targeted alarm activation without external emergency services is required, for example in industrial facilities, schools, or residential complexes.
Functions and Equipment in Detail
The detector features a swing door with an opening angle of 180°, equipped with a replaceable glass panel. This design enables easy operation and ensures clear visibility of the labelling. When activated, an integrated locking nose prevents the door from accidentally closing, securing the status indication during an alarm. Activation is achieved via a tamper-resistant microswitch configured as a changeover switch. This contact is potential-free and can be operated at a rating of 48 VAC/DC and 1 A, making it suitable for connection to various warning systems.
Technology Explained Simply
The protection rating IP43 (according to DIN EN 60 529) means the device is protected against solid foreign objects (minimum 1 mm) and against splashing water. This makes the call point suitable for use in indoor environments and sheltered outdoor areas where no direct rainfall exposure or strong mechanical stress is expected. The operating temperature range of -20 °C to +60 °C ensures reliable function under varying environmental conditions, as commonly found in many buildings. The integrated rest current monitoring ensures the contact is monitored in its resting state, enabling detection of false alarms or open contacts.
Compatibility and Accessories
The HMH-001B manual call point is compatible with various systems, including the AAS-100A, DMM-618A, and systems from the VARES series. This compatibility allows flexible integration into existing alarm infrastructures. Optional accessories include replacement glass panels and replacement keys, facilitating easier maintenance and renewal of the device. The replacement glass panel can be easily swapped in case of damage, without requiring replacement of the entire unit.
Mounting and Installation
Installation is carried out in surface-mounted configuration, with the device being mounted on a suitable wall or column. The rear terminal connection allows for simple and secure wiring. Installation does not require any special tools or additional components, as the device is delivered with all necessary hardware and software parts. The positioning should ensure the call point is easily accessible and the labelling remains clearly visible.
Operational Advantages
Using the HMH-001B provides reliable and clear alarm activation. The robust aluminium construction ensures long service life and low maintenance. The replaceable labelling and glass panel allow individual adaptation to specific requirements. Compatibility with various systems increases flexibility during planning and integration into existing safety concepts. The integrated locking nose and rest current monitoring contribute to system reliability and minimise the risk of false alarms or unintended activation.
Accessories and Alternatives
Optional accessories include replacement glass panel (part number HMG-001) and replacement key (part number HMS-001). The replacement glass panel is identical to the original and can be easily exchanged. The replacement key enables restoration of access functionality if the original key is lost.
Manufacturer and Manufacturer Number
The HMH-001B manual call point is manufactured by RCS Audio-Systems. The manufacturer’s part number is HMH-001 B. The product is made in Germany (MADE IN GERMANY). The technical specifications and functions correspond to the information provided in the manufacturer’s official data sheets and product pages.