RCS Audio-Systems ESU-002 A, EAN: 4250458207261

RCS Audio-Systems ESU-002 A emergency switching unit 2-way

100V Electro Acoustic Systems > Emergency warning systems

RCS Audio-Systems ESU-002 A emergency switching unit 2-way

Lieske Part No. 211859
Mfg Part No ESU-002 A
EAN-Code 4250458207261
Manufacturer RCS Audio-Systems
Here only 94,05 EUR
111,92 EUR incl. VAT

Further information for RCS Audio-Systems ESU-002 A emergency switching unit 2-way

Technical data
Switching voltage250 V DC per switching contact (line relay)
Switching voltage (100 V / mains relay)Relay energized: min. 16.8 V DC, max. 30 V DC; Relay de-energized: min. 0 V DC, 4.8 V DC
Switching current8 A AC per switching contact (power relay)
Switching power500 W (100 V relay)
Wire cross-section per terminal contact0.08 mm²; 2.5 mm² (without ferrule); 0.25 mm²; 1.5 mm² (with ferrule)
Dimensions (W x H x D)85 x 85 x 50 mm
Stripping length for connection wires5,6 mm
The ESU-002A from RCS Audio-Systems is an emergency switching unit, specifically developed for safety-critical public address and alarm systems. The device enables the reliable execution of two independent switching functions: switching 100V loudspeaker lines from a local program to a central alarm source, and simultaneously disconnecting two separate 230V power supplies. This function is particularly relevant in leased building complexes, where during a mandatory reception (e.g., during an alarm), tenant installations are automatically deactivated and the central alarm announcements are transmitted to loudspeakers in sub-leased areas. The unit operates using a priority relay module, which switches both 100V signals and line voltages (up to 250 V AC).

Applications
The ESU-002A is ideal for installations in multi-family houses, hotels, office buildings, or other leased properties, where central alarm notification must be carried out via a main system, while local tenant systems are deactivated during an alarm. The switching occurs automatically as soon as a mandatory reception signal (e.g., via a 16.8–30 V DC control signal) is applied to the device. Deactivating tenant amplifier systems prevents interference and ensures that only the central alarm message is transmitted.

Functions and Equipment in Detail
The device features two separate relays: one for the 100V loudspeaker line and a second for line voltage switching. The switching capacity for the 100V relay is up to 500 W, sufficient to operate typical loudspeaker lines. The line voltage relays can each switch up to 8 A AC at a switching voltage of 250 V AC. The relays are activated via a control signal: when the voltage is at least 16.8 V DC and up to 30 V DC, the relay is energized; when the voltage drops below 4.8 V DC, the relay de-energizes. This ensures a clear and reliable switching logic.

Technology Explained Simply
The ESU-002A uses a priority relay module, ensuring that during an alarm, the central alarm has priority over local programs. The 100V loudspeaker line is switched via a relay, routing the main system’s signal to the loudspeakers. Simultaneously, two separate 230V power supplies are interrupted via a second relay to deactivate local amplifier systems. The switching functions are independent of each other, so a fault in one circuit does not affect the other. The terminal connections are designed for wire cross-sections of 0.08–2.5 mm² (without wire end ferrules) and 0.25–1.5 mm² (with wire end ferrules), with a stripping length of 5.6 mm for the connecting wires. This simplifies installation and ensures a secure connection.

Compatibility and Accessories
The ESU-002A is specifically designed for integration into existing public address systems, particularly in combination with 100V central units from the VLA or VLZ series. The switching is triggered by a control signal provided by the central alarm system. The unit is compatible with standard 100V loudspeaker lines and 230V line voltage circuits. The use of wire end ferrules is optional, but recommended to ensure a stable connection.

Mounting and Installation
Installation is simple and quick thanks to easily accessible terminal contacts and defined stripping lengths. The device is compact (dimensions: 85 × 85 × 50 mm) and can be mounted at suitable locations in the installation space. The housing is made of plastic and meets the protection rating IP 66, meaning it is dust-tight and waterproof, and can therefore be used even in demanding environments, such as outdoors or in damp rooms.

Operational Advantages
The ESU-002A provides a reliable and automated priority switching function, enhancing the safety and efficiency of alarm systems. The separation of 100V audio and line voltage switching ensures clear functional separation and minimizes error sources. The high protection class IP 66 allows flexible mounting even in harsh environments. The combination of compact design and high functionality makes the ESU-002A a practical solution for professional public address systems.

Scope of Delivery
The scope of delivery includes the ESU-002A emergency switching unit and an installation manual.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/211859
qrcode für RCS Audio-Systems ESU-002 A emergency switching unit 2-way