Technical data
Height units2 HE
Power source230 V AC (50-60 Hz)
Dimensions (W x H x D)483 x 88 x 358 mm; 2 HE
Charging cut-off voltageca. 2x 27,1 V DC
Power consumption748 W
Battery capacity2x 65-320 Ah
Loading currentmax. 2x 16 A
19" rack mountingJa
The emergency power management ESP-4000 B from RCS Audio-Systems is a certified emergency power supply for voice alarm systems, meeting the requirements of standard VDE 0833-Part 4. The device is specifically designed for use in emergency warning systems and ensures reliable power supply for amplifiers and other critical components in the event of a mains failure. It is certified to EN 54-4 and also complies with standards EN 12101-10 and NFS 61940, confirming its suitability for use in public and industrial facilities.

Applications

The ESP-4000 B is used in voice alarm systems that must provide acoustic warnings via loudspeakers in emergencies. It is designed for installation in 48,3 cm ( 19 inch )-racks and offers 12 power outputs, providing high connection capacity for multiple amplifiers. The device height is 2 HE, enabling compact mounting in standard racks. The emergency power supply is designed for use in ELA enclosures (Electronic Loudspeaker Systems), where continuous power supply is required even during mains interruptions.

Functions and Equipment in Detail

The device features a digital charging unit and a switch-mode power supply, ensuring efficient and controlled power supply. The charging cut-off voltage is approximately 2x 27.1 V DC, with a maximum charging current of 2x 16 A. This enables rapid restoration of battery capacity, even with large battery sets. The battery capacity can range from 2x 65 Ah to 2x 320 Ah, and all commercially available lead-acid batteries can be used. An integrated deep discharge protection safeguards the 24-volt batteries from damage due to excessive discharge.

Technology Explained Simply

The emergency power supply continuously monitors the status of the mains voltage and the batteries. In the event of a mains failure, the device automatically switches to emergency power mode. Mains failure monitoring is performed via an integrated sensor that triggers the switch to emergency power. Battery failure monitoring includes measuring internal resistance to detect defects or aging of the batteries at an early stage. An equalization charge ensures that the voltages of individual battery cells are kept balanced, extending the battery life. A temperature sensor adjusts the permitted charging current according to the ambient temperature inside the enclosure to prevent overheating and damage.

Compatibility and Accessories

The ESP-4000 B is equipped with 12 outputs for amplifiers, each rated for up to 30 A. The rear of the device provides connections for external fault signals, an Ethernet connection (RJ-45), and a connection for a temperature sensor. Fault signal indication is provided via LED displays on the front panel and a potential-free changeover contact on the rear. Configuration of operating parameters is done via a USB interface, with the required configuration software included in the delivery scope.

Mounting and Installation

The device is designed for 48,3 cm ( 19 inch )-rack mounting and can be installed in standard racks. Dimensions are 483 mm (W) x 88 mm (H) x 358 mm (D). Power supply is via 230 V AC (50–60 Hz). Configuration is performed via the USB interface and the included software.

Operational Advantages

The fast charging function with up to 32 A (2x 16 A) enables rapid charging of batteries, even with large capacities. Fault diagnosis is performed via multiple channels: LED displays, buzzer, and fault signal contacts. This ensures quick detection and correction of faults. Certification to EN 54-4 ensures compliance with safety and functional requirements for emergency warning systems. The use of commercially available lead-acid batteries offers flexibility in battery selection. Batteries are not included in the delivery scope.