| Technical data |
| Sound pressure level (SPL) 1 W/1 m | 93,0 dB |
| Dimensions (Ø x H) | Ø 170 mm x 76 mm |
| Colour | white (similar to RAL 9010) |
| Adjustments at 100 V | 10/6/3/1,5 W |
| Impedance | 8 Ohm |
| Speaker diameter | 165 mm |
| Sound pressure level (SPL) Pmax/4 m | 100,2 dB |
| Sensitivity 1 W/4 m, EN54-24 | 81,0 dB |
| Shape | Round |
| Beam angle (-6dB, 1/2/4 kHz) | 180°/105°/ 50° |
| Rated load capacity (program) | 10 (15) W |
| Frequency range | 230 - 24.000 Hz |
The DA-110 EN is a ceiling-mounted speaker from RCS Audio-Systems, specifically developed for use in voice alarm systems (SAA). It has been tested and certified by a notified product certification body in accordance with EN 54-24:2008, making it suitable for safety-critical applications in buildings. The device features a 165 mm wideband speaker, ensuring clear voice reproduction and balanced music playback. The construction from plastic-coated metal with an integrated metal back panel enables a flat, unobtrusive installation on the ceiling, with no visible mounting edge. The speaker is white, similar to RAL 9010, allowing it to blend discreetly into many indoor environments.
Applications
The speaker is intended for use in public buildings, corridors, waiting areas, and office environments where reliable voice alarm and background music playback are required. Certification to EN 54-24:2008 and compliance with BS 5839, Part 8 ensure adherence to current standards for fire protection and alarm systems. The temperature range of –10 °C to +55 °C makes it suitable for indoor spaces with varying environmental conditions.
Functions and Equipment in Detail
The DA-110 EN features a 165 mm wideband speaker with moisture impregnation, ensuring even sound radiation and high audio quality. The impedance is 8 Ohm, with a rated power of 10 W and a music power handling of up to 15 W. The power taps at 100 V are set to 10/6/3/1.5 W, enabling flexible adaptation to various systems. The 2-pole ceramic terminal and integrated thermal fuse enhance operational safety and prevent overloads.
Technology Explained Simply
The sound pressure level is 93.0 dB at 1 W/1 m, indicating sufficient loudness for indoor spaces. At maximum power (Pmax), the speaker reaches 100.2 dB at a distance of 4 m, sufficient for clear audibility in larger rooms. The sensitivity according to EN 54-24 (1 W/4 m) is 81.0 dB, a value relevant for voice alarm system certification. The frequency range of 230 Hz to 24,000 Hz covers the entire audible spectrum, enabling natural reproduction of speech and music. The radiation angles are 180° at 1 kHz, 105° at 2 kHz, and 50° at 4 kHz, ensuring broad yet targeted sound dispersion.
Compatibility and Accessories
The speaker is designed for use in 100 V amplifier systems and can be connected via the designated power taps (10/6/3/1.5 W). Certification to EN 54-24:2008 and compliance with BS 5839, Part 8 allow integration into existing fire protection and alarm systems. The device is equipped with a metal back panel, enabling stable ceiling mounting.
Installation and Mounting
Installation is carried out by screwing the integrated metal back panel, enabling quick and uncomplicated setup. The flat design with a mounting height of 76 mm and a diameter of 170 mm ensures a discreet installation that blends well into the ceiling surface. The protection class IP21C protects against finger contact and splashing water, making it suitable for indoor use.
Operational Advantages
The DA-110 EN offers excellent speech intelligibility, which is crucial for alarm systems. The combination of wideband speaker and moisture impregnation ensures reliable and high-quality sound reproduction. The integrated thermal fuse and 2-pole ceramic terminal enhance safety and extend the device's service life. Certification to EN 54-24:2008 and compliance with BS 5839, Part 8 ensure adherence to current standards and facilitate approval by authorities and supervisory bodies.