| General |
| Input voltage | 24 V DC |
| Nominal voltage | 24 V DC |
| Nominal current | 9 mA |
| Response time | 5 ms |
| Release time | 8 ms |
| Contact type | 1 PDT |
| Contact material | AgSnO |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 5 V |
| Minimum switching current | 10 mA |
| Limit current | 6 A |
| Switching power (ohmic load) | 140 W |
| Dielectric strength | 4 kV AC |
| Operation temperature | -40 to 60 °C |
| Storage and transport temperature | -40 to 85 °C |
| Mechanical life | 2 x 10^7 Switching cycles |
| Connection method | Push-in connection |
| Minimum cross-section | 0,14 mm² |
| Maximum cross-section | 2,5 mm² |
| Trimming length | 8 mm |
| Mounting method | DIN rail NS 35/7.5 |
| Pollution degree | 3 |
| Surge voltage category | III |
| Standards | IEC 60664, DIN VDE 0110, DIN EN 50178/VDE 0160, IEC 60255 |
| Approvals | CUL, CUL Listed, UL, UL Listed |
| Construction type | plug-in miniature relay with base terminal |
The product PLC-RPT- 24DC/21 from Phoenix Contact is a PLC interface, consisting of a base terminal PLC-BPT.../21 with push-in connection and a pluggable miniature relay with power contact. It is designed for mounting on the support rail NS 35/7,5 and features a changeover contact (1 PDT). The input voltage is 24 V DC, making it suitable for use in industrial control systems and automation applications where galvanic isolation between control and load circuit is required.
Applications
This PLC interface is used in industrial electrical engineering, particularly in control systems, where it serves as an interface between a control system (e.g. PLC) and a load circuit. It enables signal transmission with galvanic isolation, minimizing disturbances in the control circuit and increasing safety. Applications include manufacturing automation, building automation, or machine control, where safe and reliable signal transmission is required.
Functions and Equipment in Detail
The device consists of a base terminal with push-in connection, enabling quick and secure wiring. The maximum permissible cross-section is 2.5 mm² for single- and multi-strand conductors, with a minimum cross-section of 0.14 mm². The wire stripping length is 8 mm. The pluggable miniature relay is equipped with a power contact suitable for operating loads such as heaters, motors, or contactors. The contact type is a single changeover (1-PDT), with the contact material being silver-tin oxide (AgSnO).
Technology Explained Simply
The relay coil is operated at 24 V DC, with a typical current consumption of 9 mA. The pickup time is typically 5 ms, and the release time is 8 ms. The contact side is rated for maximum switching voltages of 250 V AC/DC. When switching voltages exceed 250 V (e.g. L1, L2, L3) between identical terminal blocks in adjacent modules, installation of a partition plate PLC-ATP is required to safely avoid potential bridges. The contact load capacity is up to 140 W at 24 V DC for resistive loads, with values for other voltages specified accordingly. The mechanical life is 2 × 10⁷ switching cycles. The insulation strength between coil and contact is 4 kV AC (50 Hz, 1 min). The operating temperature range is -40 °C to 60 °C, and the storage and transport temperature range is -40 °C to 85 °C.
Compatibility and Accessories
The PLC interface is designed for mounting on the support rail NS 35/7,5. Compatible accessories include feed-in terminals such as PLC-ESK GY, single jumper bridges in various colors and lengths (e.g. FBST 8-PLC GY, FBST 6-PLC BU), endless jumper bridges (e.g. FBST 500-PLC BU), terminal markings (e.g. UCT-TM 6, UC-TM 6 CUS), and system connectors such as PLC-V8/FLK14/OUT/M. For mounting on the support rail, various DIN rails are available, including unperforated and perforated variants made of steel or copper.
Mounting and Installation
Mounting is done on the support rail NS 35/7,5, with modules able to be mounted in rows without spacing. Wiring is done via the push-in connection, allowing quick and secure connection without tools. The device can be positioned freely, as no specific mounting orientation is required. Installation is carried out in electrical switchgear complying with standards IEC 60664, DIN VDE 0110, DIN EN 50178/VDE 0160, and IEC 60255.
Advantages in Operation
The PLC interface offers high operational safety through galvanic isolation between control and load circuit. The push-in technology enables fast and error-free wiring. The mechanical life of 2 × 10⁷ switching cycles ensures long service life. Compatibility with various accessories and mounting on standard support rails increases installation flexibility.