v_shortname: Zener barrier, device offers intrinsically safe circuits for device protection level: Ga , Gb , Gc , Da , Db , Dc , Ma , Mb, device suitable for installation in device protection level: Gc, device offers intrinsically safe circuits for division: Div. 1 , Div. 2, device suitable for installation in division: Div. 2, type: DC version, positive polarity, number of channels: 2, supply circuit: max. 27 V, measuring circuit: max. 26.5 V at 10 µA, nominal resistance: 300 O, series resistance: terminals 1, 8: max. 327 O, nominal fuse current: 50 mA, design: modular terminal housing, see system description, mounting: on 35 mm top hat rail in accordance with EN 60715:2001