The ICF-1150I-M-SC-T-IEX is a premium industrial serial-to-fiber converter that bridges RS-232/422/485 devices to multimode fiber networks via SC connector. Designed for hazardous environments, this model features 2 kV galvanic isolation and is certified for IECEx and ATEX Zone 2, making it a trusted choice for mission-critical industrial applications.
With an extended operating temperature range of -40 to 85°C, the converter is engineered for extreme conditions. It supports automatic RS-485 data direction control (ADDC), multiple selectable pull-up/down resistors, and configurable termination resistance, ensuring high adaptability in serial communication infrastructures.
Technical Specifications (English):
Serial Interface:
- Number of Ports: 2
- Standards Supported: RS-232, RS-422, RS-485
- Baudrate: 50 bps to 921.6 kbps (including non-standard rates)
- Flow Control: ADDC (automatic data direction control) for RS-485
- Connectors: 5-pin terminal block, SC (multimode)
- Isolation: 2 kV galvanic isolation (I models)
RS-485 Configuration:
- Pull High/Low Resistors: 150 kΩ, 10 kΩ, 4.7 kΩ, 3.3 kΩ, 1 kΩ, 909 Ω, 822 Ω, 770 Ω, 500 Ω, 485 Ω
- Terminator Options: N/A, 120 Ω, 120 kΩ
Serial Signals:
- RS-232: TxD, RxD, GND
- RS-422: Tx+, Tx-, Rx+, Rx-, GND
- RS-485-4W: Tx+, Tx-, Rx+, Rx-, GND
- RS-485-2W: Data+, Data-, GND
Power Requirements:
- Input Voltage: 12 to 48 VDC
- Max. Input Current: 300 mA
- Number of Inputs: 1
- Connector: Terminal block
- Protection: Overload and reverse polarity supported
Physical Characteristics:
- Housing: Metal
- IP Rating: IP30
- Dimensions: 30.3 × 70 × 115 mm (1.19 × 2.76 × 4.53 in)
- Weight: 330 g (0.73 lb)
- Mounting: DIN-rail
Environmental Limits:
- Operating Temperature: -40 to 85°C (-40 to 185°F)
- Storage Temperature: -40 to 85°C (-40 to 185°F)
- Humidity: 5 to 95% (non-condensing)
Certifications:
- EMC: EN 55032/35
- EMI: CISPR 32, FCC Part 15B Class A
- EMS: IEC 61000-4-2 to -4-8
- Safety: UL 61010-2-201
- Environmental Tests: IEC 60068-2-1, -2, -3
- Vibration: IEC 60068-2-6
- Hazardous Locations: UL/cUL Class I Div. 2 Groups A/B/C/D, ATEX Zone 2, IECEx
MTBF:
- 792,085 hours (Telcordia/Bellcore standard)
Warranty:
- 5 years (details at www.moxa.com/warranty)