Further information for Moeller DILEM4(230V50/60HZ) (052506)
Power contactor, Application: Miniature contactor for motors and resistive loads, DILEM power contactors, Utilization category: AC-1: Non-inductive or slightly inductive load, resistance furnaces, AC-3: Squirrel cage motors: Starting, switching off during operation, AC-4: Squirrel cage motors: Starting, plugging, reversing, inching, Connection technology: Screw terminals, Poles: 4-pole, Rated operating current AC-3 380 V 400 V: Ie= 9 A, Rated operating current AC-1 conventional thermal current, 3-pole, 50 - 60 Hz open at 40 °C: Ith = Ie= 22 A, encapsulated: Ith= 16 A, Rated operating current AC-1 conventional thermal current 1-pole open: Ith= 60 A, encapsulated: Ith= 50 A, max. Rated operating power Three-phase motors 50 - 60 Hz AC-3 220 V 230 V: P= 2.2 kW, 380 V 400 V: P= 4 kW, 660 V 690 V: P= 4 kW, max. rated operating power Three-phase motors 50 - 60 Hz AC-4 220 V 230 V: P= 1.5 kW, 380 V 400 V: P= 3 kW, 660 V 690 V: P= 3 kW, can be used for: .DILEM, .DILE, current type AC/DC: alternating current operation