Further information for BTR KRS1-E08 HR3 0-1-2 - threshold
The threshold switch is used to switch units, pumps, fans, burners, etc. As soon as the input voltage reaches the switching threshold, the relay switches on. If the input voltage falls below the switch-off threshold, the relay switches off again. The module is designed for two-stage control via an analog 0 to 10 V DC control signal. Connection with screw terminals, control signal 0 V DC = no stage active (OFF), control signal 5 V DC = stage 1 active, control signal 10 V DC = stage 1 and stage 2 active, with manual control level