Further information for BTR 1102810520 - CPW E12 230VAC 1 10a 1We 250VAC / 4A cosPhi Keeper
The cosPhi monitor is used to detect underload. The response value and response time are adjustable. It can also be used in conjunction with a frequency converter (frequency 2 to 200 Hz). Monitoring is carried out by detecting the phase shift between current and voltage. This phase angle shifts with the load on a motor. Function settings via bridges S1 - S2 - S3: S1 - S2 open = relay de-energized in the event of underload, S1 - S2 bridged = relay energized in the event of underload, S1 - S3 open = with error memory, S1 - S3 bridged = without error memory. The module can be remotely unlocked using a normally open contact on S1 - S3. With the error memory (no bridge over S1-S3), the error message remains until acknowledged or until the supply voltage is interrupted.