| General |
| Nominal voltage | 450/750 V |
| Test voltage | 2500 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Operation temperature | +70 °C |
| Bending radius | 15 x cable diameter |
| Flame retardancy | according to VDE 0472 T. 804 test type B (=IEC 332-1) |
| Conductor | bare copper, fine-stranded |
| Insulation | PVC according to VDE 0207 |
The H07V-K 50,0 GNGE TR is a PVC-insulated single-core cable from manufacturer LTC, designed for use in dry rooms as well as in control and distribution systems. It is suitable for installation in conduits, both above and below plaster, and in closed installation channels. The cable is used for internal wiring of devices, control panels, and distributors, as well as for protected installation in and on lighting fixtures. The maximum rated voltage is 1000 V AC or 750 V DC to earth. Direct installation on trays, gutters, or troughs is not intended.
Applications
This cable is intended for indoor use, particularly in electrical installations where protected routing in conduits or channels is ensured. It is commonly used in building electrical engineering, for example in wiring distributors, enclosures, or lighting systems. Use is limited to dry environments; the cable is not suitable for direct outdoor installations or damp areas.
Functions and Features in Detail
The cable consists of a bare, fine-stranded copper conductor, providing high electrical conductivity and flexibility. Insulation is provided by PVC in accordance with VDE 0207, ensuring good mechanical and electrical insulation. The sheath color complies with VDE 0293 standards, with green/yellow (GNGE) designated for the protective conductor. This color coding is standardized in electrical engineering and ensures clear identification of the protective conductor.
Technical Explanation
The rated voltage of 450/750 V means the cable is designed for electrical systems operating up to 450 V between conductors and up to 750 V between a conductor and earth. The test voltage of 2500 V ensures quality control and confirms the insulation remains stable even under increased voltage. The maximum operating temperature is +70 °C, making the cable suitable for use under normal indoor conditions. During installation, the temperature must be between +5 °C and +70 °C; after installation, the cable can be operated down to -30 °C, provided the maximum operating temperature is not exceeded. The minimum bending radius is 15 times the cable diameter, allowing flexible installation without damaging the cable. Flame retardancy according to VDE 0472 T. 804 test method B (equivalent to IEC 332-1) ensures the cable is not easily ignitable and does not propagate flame in case of fire.
Compatibility and Accessories
The cable is designed for standard installations and is compatible with common installation conduits, distributors, and control panels. It can be combined with other cables of type H07V-K, especially in multi-conductor installations. The green/yellow color identifies it as a protective conductor, used in electrical systems for grounding devices and control panels. Use in combination with other cables must comply with VDE guidelines and applicable standards for electrical installations.
Installation and Mounting
Installation must take place in closed conduits or channels; the cable must not be laid directly on trays, gutters, or troughs. The installation must protect the cable from mechanical stress, moisture, and direct sunlight. The minimum temperature for installation is +5 °C to ensure undamaged laying. After installation, the cable can be operated at temperatures down to -30 °C, as long as the maximum operating temperature of +70 °C is not exceeded.
Operational Advantages
The cable offers high electrical conductivity due to the fine-stranded copper conductor and reliable insulation via PVC. Flame retardancy according to VDE 0472 T. 804 test method B increases operational safety. The green/yellow color enables clear identification of the protective conductor, simplifying maintenance and inspection. Flexibility from the fine-stranded conductor and the specified bending radius facilitate installation in complex routing situations.