| General |
| Nominal voltage | 450/750 V |
| Test voltage | 2500 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Operation temperature | +70 °C |
| Bending radius | 15 x cable diameter min. |
| Flame retardancy | VDE 0472 T. 804 test type B (=IEC 332-1) |
| Conductor | bare copper, fine-stranded |
| Insulation | PVC according to VDE 0207 |
| Sheath colour | light blue RAL 5015 |
| Application | installation in dry rooms, switching and distribution installations, in conduits above and below plaster, as well as in closed installation channels |
The H07V-K 1.5 HBL RAL 5015 is a PVC-insulated single-core cable from manufacturer LTC, designed for use in dry rooms as well as in control and distribution systems. It is suitable for installation in conduits, both above and below plaster, and in closed installation channels. The cable is used for internal wiring of devices, control panels, and distributors, and is also intended for protected installation in and on luminaires. The maximum rated voltage is 1000 V AC or 750 V DC to earth. Direct installation on trays, troughs, or channels is not intended.
Applications
This cable is designed for indoor use, particularly in electrical installations where stable and reliable connections are required. It is commonly used in residential and commercial buildings to connect electrical devices, lighting systems, and distributors. Installation takes place in closed channels or conduits to minimize mechanical stress and environmental influences. The cable is not suitable for outdoor use or in damp areas, as it is not designed for direct outdoor installation.
Functions and Equipment in Detail
The single-core cable consists of a fine-stranded, bare copper conductor, ensuring high electrical conductivity. Insulation is provided by PVC, specified according to VDE 0207, to ensure sufficient electrical insulation and mechanical stability. The sheath color complies with VDE 0293 and is finished in light blue (RAL 5015), enabling easy identification and assignment in complex installations. The color serves as a visual identifier, especially in systems where multiple cables are run in parallel.
Technology Explained Simply
The rated voltage of the cable is 450/750 V, meaning it is designed for electrical systems with a maximum voltage of 450 V between conductors and 750 V between the cable and earth. The test voltage of 2500 V serves as a safety margin to verify insulation strength under load. The maximum operating temperature is +70 °C, and the cable may be installed at temperatures between +5 °C and +70 °C. After installation, the cable can be operated at temperatures from -30 °C to +70 °C. The minimum bending radius is 15 times the cable diameter to prevent damage to the conductor or insulation. Flame retardancy corresponds to test method B according to VDE 0472 Part 804 (equivalent to IEC 332-1), meaning the cable does not produce a flammable flame and does not propagate flame during a flame application test.
Compatibility and Accessories
The cable is designed for use in standard installations and can be processed using common installation techniques and tools. It is compatible with standard terminals, connectors, and other connection elements designed for PVC-insulated cables. The light blue color (RAL 5015) corresponds to the marking for protective earth conductors (PE) according to VDE 0293, making it suitable for use as a protective conductor in electrical systems. The cable is not intended for use in explosive atmospheres.
Installation and Mounting
Installation takes place in closed installation channels, conduits, or in-wall installation below plaster. The cable must be routed to avoid mechanical stresses such as bending or compression. The minimum bending radius of 15 times the cable diameter must be observed to ensure the integrity of the insulation and conductor. Installation is carried out at temperatures between +5 °C and +70 °C. After installation, the cable must be operated at temperatures between -30 °C and +70 °C. The cable is not intended for direct installation on open supports such as trays or troughs.
Operational Advantages
The cable offers high electrical conductivity due to the fine-stranded copper conductor and reliable insulation via PVC. Flame retardancy according to VDE 0472 Part 804, test method B, provides enhanced safety in case of fire. The light blue color (RAL 5015) facilitates identification, especially in complex systems where cable assignment is critical. The cable is designed for use in dry indoor environments and offers long service life when installed and used correctly within the specified operating conditions.