| General |
| Nominal voltage | 450/750 V |
| Test voltage | 2500 V |
| Operation temperature | +70 °C |
| Installation temperature range | +5 to +70 °C |
| Temperature range after installation | -30 to +70 °C |
| Bending radius | 15 x cable diameter |
| Flame retardancy | according to VDE 0472 T. 804 test type B |
| Conductor | bare copper, fine-stranded |
| Insulation | PVC according to VDE 0207 |
| Sheath colour | Black |
| Application | installation in dry rooms, switching and distribution installations, in conduits above and below plaster, as well as in closed installation channels |
The H07V-K 1.5 SW is a PVC-insulated single-core cable from manufacturer LTC, designed for use in dry indoor environments for electrical installations and control systems. It is used for internal wiring of devices, control systems, and distributors, as well as for protected installation in and on lighting fixtures. The cable is rated for a nominal voltage up to 1000 V AC or 750 V DC against earth and is suitable for installation in conduits, under plaster, on plaster, or in closed installation channels. Direct installation on trays, gutters, or troughs is not intended.
Applications
This cable is used in electrical installations for operation in dry rooms, particularly in control and distribution systems. It is suitable for connecting electrical devices, for internal equipment of machines and appliances, and for wiring in lighting installations. Installation takes place in protected environments; the cable is not intended for direct outdoor applications or damp areas.
Functions and Features in Detail
The cable consists of a bare, fine-stranded copper conductor, ensuring high flexibility and good electrical conductivity. Insulation is provided with PVC according to VDE 0207, ensuring high mechanical strength and chemical resistance. The sheath color complies with VDE 0293 standards, enabling clear identification of the cable within the installation network. The color black is standard.
Technical Explanation
The nominal voltage of 450/750 V defines the maximum voltage the cable can safely transmit. The test voltage of 2500 V is used for quality testing and ensures insulation strength. The maximum operating temperature is 70 °C; during installation, the cable may be used at temperatures between +5 °C and +70 °C. After installation, the ambient temperature may drop to -30 °C without damaging the cable. The minimum bending radius is 15 times the cable diameter, allowing flexible installation. Flame retardancy according to VDE 0472 T. 804, test method B (equivalent to IEC 332-1), ensures the cable does not propagate live flame when exposed to fire.
Compatibility and Accessories
The cable is supplied as a single core and can be used in combination with other cables of type H07V-K in multi-cable installations. As an alternative, the H07V-K 1.5 mm² black Eca 100 m carton is available, also suitable for the same applications. Another variant is the H07V-K 1x 1.5 black 100 m reel, also with 450/750 V nominal voltage and PVC insulation.
Installation and Mounting
Installation is carried out in closed channels, conduits, or under plaster. The cable must not be installed directly on unprotected supports such as trays or gutters. Installation is performed at temperatures between +5 °C and +70 °C. After installation, the cable remains operational even at ambient temperatures down to -30 °C. The bending radius of 15 times the cable diameter must be observed to avoid mechanical damage.
Operational Advantages
The PVC insulation provides high mechanical and chemical resistance. The fine-stranded copper structure ensures flexibility and long service life. Flame retardancy according to VDE 0472 T. 804 test method B increases safety in case of fire. The cable is optimized for use in dry indoor environments and meets the requirements for electrical installation cables in control and distribution systems.