| General |
| Conductor | Copper stranded wire, fine-stranded, class 5 |
| Wire insulation | Rubber compound according to VDE 0207 T. 20 |
| Conductor marking | according to VDE 0293-308 |
| Outer sheath | Rubber compound according to VDE 0207 T. 21 |
| Sheath colour | Black |
| Nominal voltage | 450/750 V |
| Test voltage | 2500 V |
| Installation temperature range | -25 °C |
| Temperature range after installation | -25 °C |
| Maximum operating temperature | +80 °C |
| Minimum bending radius | 6 x cable diameter |
| Continuous load max. | 15 N/mm² |
| Flame retardancy | according to VDE 0472 T. 804, test type B (=IEC 332-1) |
| Oil resistance | according to VDE 0472 T. 803, test type A |
| Ozone resistance | according to VDE 0472 T. 805, test type A or A1, test type C |
| Number of cores | 4 |
| Cross-section per conductor | 95 mm² |
| Protective conductor | gn-ge |
The H07RN-F 4G95 TR rubber-sheathed cable from LTC is a robust, flexible cable designed for use under extreme mechanical and thermal stresses. It is suitable for connecting equipment in agricultural, industrial, and fire-hazardous facilities. Typical applications include large cooking kettles, heating plates, handle lights, electric tools such as circular saws and drills, household appliances, as well as portable motors or machines on construction sites and in agricultural operations. The cable is also suitable for fixed installation, for example on plaster, in temporary buildings or prefabricated housing, and can be directly installed on components of lifting equipment and machinery.
Applications
The cable is designed for applications involving high mechanical stresses, such as tension, bending, and abrasion, as well as thermal loads. It is frequently used in environments where high flexibility and durability are required, such as in agriculture, construction, or industrial production facilities. Use in fire-hazardous areas is permitted, as the cable meets the requirements for flammability behavior according to VDE 0472 T. 804, test method B (equivalent to IEC 332-1).
Functions and Equipment in Detail
The cable features fine-stranded copper conductors of class 5, ensuring high flexibility and mobility. The conductors are insulated with a rubber compound according to VDE 0207 T. 20, and the conductor identification follows VDE 0293-308. The outer sheath consists of a rubber compound according to VDE 0207 T. 21 and is black in color. The designation 4G95 indicates that the cable has four conductors, each with a cross-section of 95 mm², with one of the conductors serving as a protective earth conductor (gn-ge).
Technology Explained Simply
The rated voltage is 450/750 V, indicating the maximum voltage at which the cable can be safely operated. The test voltage of 2500 V is used for quality testing and ensures that the insulation has the required electrical strength. The maximum operating temperature is +80 °C, and the cable can be installed and operated at temperatures ranging from -25 °C to +80 °C. The minimum bending radius is 6 times the cable diameter, enabling flexible installation. The continuous tensile load is limited to a maximum of 15 N/mm², considering the total copper cross-section. The cable is oil-resistant according to VDE 0472 T. 803, test method A, and ozone-resistant according to VDE 0472 T. 805, test methods A and A1, test method C, ensuring high resistance to environmental influences.
Compatibility and Accessories
The cable is designed for use with electrical devices and machines requiring a robust and flexible power supply. It can be combined with suitable connectors, cable lugs, and other connection elements appropriate for the rated voltage and cross-section. The use with protective conductors is ensured by the integrated protective earth conductor (gn-ge).
Installation and Mounting
The cable can be installed flexibly, with the minimum bending radius of 6 times the cable diameter being observed. Installation is carried out at temperatures between -25 °C and +80 °C, and the cable can be directly mounted on components of machinery or lifting equipment. Installation does not require special tools, but compliance with technical data and regulations of the relevant standards (e.g. VDE 0207, VDE 0472) is mandatory.
Advantages in Operation
The cable is characterized by high mechanical and thermal load capacity, enabling long service life and reliable operation even under difficult conditions. Oil and ozone resistance increases service life in environments with chemical influences. The flexible class 5 copper stranded conductor ensures high mobility, facilitating installation and use in moving applications. The protective earth conductor ensures a safe electrical connection and meets the requirements for the protective conductor in electrical installations.