General
Nominal voltage450/750 V
Test voltage2500 V
Installation temperature range-25 to +80 °C
Temperature range after installation-25 to +80 °C
Operation temperature+80 °C
Bending radius6 x cable diameter -
Continuous load15 N/mm²
Flame retardancyVDE 0472 T. 804, test type B -
Oil resistanceVDE 0472 T. 803, test type A -
Ozone resistanceVDE 0472 T. 805, test type A or A1, test type C -
ConductorCopper stranded wire, fine-stranded, class 5 -
Wire insulationRubber compound according to VDE 0207 T. 20 -
Conductor markingaccording to VDE 0293-308 -
Outer sheathRubber compound according to VDE 0207 T. 21 -
Sheath colourBlack -
The rubber hose cable H07RN-F 1X16 QMM 500M from LTC is a robust, flexible cable designed for use under extreme mechanical and thermal loads. It is suitable for connecting equipment in agricultural, industrial, and fire-hazardous facilities. Typical applications include large cooking kettles, heating plates, hand lamps, electric tools such as circular saws or drills, household appliances, as well as portable motors and machines on construction sites. The cable is also suitable for fixed installation, for example on plaster, in temporary buildings or prefabricated housing, and can be directly installed on components of lifting equipment and machinery.

Applications

The cable is designed for use in environments with high mechanical and thermal loads. It is frequently used in agriculture, industry, and construction, where high flexibility, tensile strength, and resistance to external influences are required. Use in fire-hazardous areas is permitted, with the fire behaviour test according to VDE 0472 T. 804, test type B (equivalent to IEC 332-1), confirming the appropriate safety class. The cable is also suitable for outdoor use, as it is resistant to oil and ozone.

Functions and Equipment in Detail

The cable consists of a fine-stranded copper conductor of class 5, providing high flexibility and mobility. The core insulation is made of a rubber compound according to VDE 0207 T. 20, offering good electrical insulation and mechanical stability. Core identification follows VDE 0293-308, enabling clear identification of the cores. The outer sheath is made of a rubber compound according to VDE 0207 T. 21 and is black in colour. The sheath structure ensures high mechanical strength and resistance to external influences.

Technology Explained Simply

The rated voltage is 450/750 V, indicating the maximum voltage the cable can safely transmit. The test voltage of 2500 V serves as a safety margin and is used during quality testing. The maximum operating temperature is +80 °C, with the cable being installable at temperatures from -25 °C to +80 °C. The minimum bending radius is 6 times the cable diameter, enabling flexible installation. The continuous tensile load is limited to a maximum of 15 N/mm², considering the total copper cross-section. Oil resistance according to VDE 0472 T. 803, test type A, and ozone resistance according to VDE 0472 T. 805, test type A or A1, test type C, ensure long service life in industrial environments.

Compatibility and Accessories

The cable is suitable for use with standard plugs and cable lugs designed for a cross-section of 16 mm². Use with other cable types or accessories is only possible if the electrical and mechanical requirements of the respective standards are met. The cable is supplied without a protective conductor (X), as indicated in the type designation H07RN-F 1X16 QMM 500M. For applications requiring a protective conductor, the variant with protective conductor (G) should be selected.

Installation and Mounting

Installation is carried out by direct laying on components, plaster surfaces, or in temporary buildings. The cable can also be laid on machines and lifting equipment. During installation, a minimum bending radius of 6 times the cable diameter must be observed to ensure mechanical integrity. Installation is performed at temperatures between -25 °C and +80 °C, with the operating temperature not exceeding +80 °C. The cable is suitable for fixed installation, but not for mobile applications involving high dynamic loads.

Advantages in Operation

The cable offers high mechanical strength and resistance to external influences such as oil, ozone, and mechanical stress. The flexible copper conductor of class 5 enables high mobility, making it suitable for mobile applications. The high temperature resistance and fire behaviour test according to VDE 0472 T. 804, test type B, increase operational safety. The black-coloured rubber compound of the outer sheath provides good visibility and resistance to UV radiation and mechanical damage.