Further information for Lapp 2212070 ÖLFLEX TRAY II CY 7G4 Trayflex
Certifications
EAC certification number
ЕАЭС RU С-DE.АЮ64.В.00091/19
UL AWM certification
20886 according to UL 758 (e-file number: E100338)
cUL certification
cUL CIC/TC 600V according to CSA C22.2 No. 239 (e-file number: E171371)
CSA certification
AWM II B according to CSA C22.2 No. 210, AWM I A according to CSA C22.2 No. 210, AWM I B according to CSA C22.2 No. 210, AWM II A according to CSA C22.2 No. 210
CE marking
EAC-certified
UL recognized
UL listed
cUR recognised
cUL listed
CSA certified
VDE certified
HAR certified
Ecolab certified
Electrical characteristics
Nominal voltage
U0/U: 0,6/1 kV AC rms according to IEC
Rated voltage
600 V AC rms according to UL TC, 600 V AC rms according to c(UL) CIC/TC, 600 V AC rms according to UL MTW, 1000 V AC rms according to UL WTTC, 1000 V AC rms according to UL AWM, 1000 V AC rms according to CSA AWM
Test voltage
2 kV
Current rating according to
NEC / NFPA 70, NFPA 79, IEC 60364-5-52
Max. conductor resistance at 20°C
5.09 Ω/km
General information
Brand
ÖLFLEX®
Product type
Power and control cable
Weight
499 kg/km
Copper index
310.2 kg/km
Industry segment
Construction Machinery, Power Grids, Food & Beverage, Healthcare & Pharma, Intralogistics, Machine tools, Packaging, Processing Industries, Robotics
Product characteristics
Application area
Flexible, Fixed installation, Torsion
Suitable for use in accordance with NEC chapter 5
Class I Division 2
Minimum bending radius, stationary
6 x outer diameter
Minimum bending radius in mm, fixed installation
97.6 mm
Minimum bending radius, occasionally flexing
6 x outer diameter
Minimum bending radius in mm, occasionally flexing
97.6 mm
Torsion
for +/- 150 °/m and min. 5 °C up to 5000 Torsion cycles, for +/- 150 °/m and min. -40 °C up to 2000 Torsion cycles
Temperature, fixed installation
-40 °C to 70 °C max. conductor temperature according to IEC, -25 °C to 90 °C max. conductor temperature according to UL MTW, -40 °C to 105 °C max. conductor temperature according to CSA AWM, -25 °C to 90 °C max. conductor temperature according to UL/CSA TC, -40 °C to 105 °C max. conductor temperature according to UL AWM
Temperature, fixed installation min
-40 °C
Temperature, fixed installation max
105 °C
Temperature, occasionally moved
-25 °C to 70 °C max. conductor temperature according to IEC, -25 °C to 105 °C max. conductor temperature according to CSA AWM, -25 °C to 90 °C max. conductor temperature according to UL MTW, -25 °C to 90 °C max. conductor temperature according to UL/CSA TC, -25 °C to 105 °C max. conductor temperature according to UL AWM
Temperature, occasionally moved min
-25 °C
Temperature, occasionally moved max
105 °C
Storage temperature min.
-40 °C
Max. storage temperature
40 °C
Flame retardance according to
UL Vertical-Tray Flame Test, CSA FT4, IEC 60332-3-24
UV-resistant according to
UL sunlight resistant, EN 50525-1 (cables with a black sheath are suitable for permanent outdoor use)