Further information for JUNG 400041SE - KNX button interface 4 way
4-way button interface
KNX 4-way button interface
Intended use
¦ Inputs for querying conventional, potential-free contacts in KNX systems and sending telegrams to the KNX bus to report statuses, meter readings, operating consumers, etc.
¦ Outputs for controlling LEDs
¦ Installation in a device box with dimensions in accordance with DIN 49073 in combination with a suitable cover
¦ When installing behind switch and button inserts, use a device box with sufficient installation depth
Product features
¦ Independent channels that work as inputs or outputs depending on the ETS parameterization
¦ Common reference potential for all channels
¦ Locking of individual channels
¦ Supply via bus, no additional supply voltage required
¦ KNX Data Secure compatible from ETS 5.7.7 or from ETS 6.1.0
¦ Can be updated with ETS service app
Outputs
¦ Connection of LED e.g. LED lamp, 5 V DC, 2.2 mA
¦ Short-circuit-proof, overload-proof and protected against
reverse polarity ¦ Parallel switching of outputs possible for consumers with higher power requirements
Inputs
¦ Connection of potential-free contacts such as buttons, switches or reed contacts
¦ The query with a pulse current avoids contact contamination (formation of an oxide layer) on the connected contacts
¦ Operating functions: switching, dimming, blind, scene or room temperature control
¦ Value transmitter for dimming, color temperature, RGBW, temperature or brightness values
¦ Transmission of the current input status after bus voltage failure
¦ Connection of door or window contacts for evaluating the status open, closed, tilted and handle position
¦ Connection of leakage, condensation and temperature sensors
¦ Pulse counter with main and intermediate counter
¦ Combination of adjacent input channels when connecting buttons, door or window contacts
¦ Logic functions
Technical data
Ambient temperature: -5 ... +45 °C
Storage/transport temperature: -25 ... +75 °C
Degree of protection: IP20
Protection class: III
Number of channels: 4
Output voltage: DC 5 V SELV
Output current per channel: max. 3.2 mA
LED current (red LED with 1.7 V forward voltage): 2.2 mA per output
Length of cable set: 25 cm, extendable to max. 30 m
Recommended cable: JY(St)Y 2x2x0.8
Dimensions (W x H x D): 43 x 28.5 x 15.4 mm
KNX medium: TP 256
Commissioning mode: S-Mode
Nominal voltage KNX: DC 21 ... 32 V SELV
Current consumption KNX: 5 ... 12 mA
Manufacturer: JUNG