REG housing 4 TE
extension module for 4-way analog output Item no.: 2204.01 REGA
Function
The analog output module extends a 4-way KNX analog output by four analog outputs that can be parameterized using software.
Received data is converted into the output signals 0 ... 1 V, 0 ... 10 V, 0 ... 20 mA or 4 ... 20 mA.
These analog output signals enable actuators in heating, air conditioning and ventilation technology to adapt their output variables based on bus information and to participate in control processes.
The output variables can be forced.
The evaluation of the module data itself and the processing of the forced control takes place in the KNX analog output.
The analog output module is connected to the KNX device using a system plug included in the scope of delivery.
Outputs that are not required can be switched off.
Voltage outputs are monitored for short circuits.
The output state is displayed by status LEDs.
Connectable analog actuators
Do not connect any electronic ballasts or electronic transformers with a 1 ... 10 V control input to the outputs!
Do not connect any external voltages to the outputs. Connected components must ensure safe isolation from other voltages.
Current outputs may be loaded with a maximum of 500 ?.
Voltage outputs must be loaded with a minimum of 1 k?.
The GND terminals of the outputs K1 ... K4 are connected internally.
If a voltage output is short-circuited between K1 ... K4 and GND, the respective output is switched off.