| General |
| Type of device | Energy meter |
| Construction type | DIN rail mounting device |
| Supply voltage | 24 V DC |
| Voltage measurement inputs | 3 |
| Current measurement inputs | 8 |
| Current measurement range | 5 mA... 6 A |
| Current resolution | 0.1 mA |
| Nominal current | 5A / 1A |
| Harmonic analysis | up to the 127th harmonic |
| Voltage measurement category | 1000 V CAT III |
| Current measurement category | 300 V CAT II |
| Measurement data storage | 4 GB |
| Multifunction inputs | 4 |
| Digital inputs | 4 |
| Digital outputs | 4 |
| Analogue output | 1 |
| Ethernet connections | 2 |
| Interface | OPC UA |
| Power supply types | TN, IT, TT |
| 3-phase 4-wire system | up to 480 V/830 V (±10%) |
| 3-phase 3-wire system | up to 690 V (±10%) |
| Accessories | installation instructions, bus connector, end angle |
| Software | GridVis Essential |
The Janitza UMG 801 base unit 8TE is a modularly expandable energy metering device, specifically developed for use in energy monitoring systems. It enables precise capture and analysis of electrical energy parameters in industrial and commercial installations. The device is designed for DIN rail mounting and fits into standard 19-inch racks as well as DIN rails, allowing flexible integration into existing switchgear. The device dimensions are 145 mm (width) × 90 mm (height) × 76 mm (depth), enabling compact installation in enclosures. Power supply is via an external power source at 24 V DC, ensuring simple and safe integration into existing 24-V networks.
Applications
The UMG 801 base unit is designed for use in electrical networks of categories TN, IT, and TT, making it suitable for a wide range of applications in industry, commerce, and infrastructure. It measures electrical parameters in 3-phase 4-wire systems up to 480 V/830 V (±10 %) and in 3-phase 3-wire systems up to 690 V (±10 %), in accordance with IEC standards. The voltage measurement category is 1000 V CAT III, ensuring safe measurement in medium-voltage networks. The current measurement category is 300 V CAT II, sufficient for measurements on supply lines and consumers in low-voltage systems.
Functions and Equipment in Detail
The device features 3 voltage input channels and 8 current input channels, organized in two groups of four. Current measurement is performed in the range of 5 mA to 6 A with a resolution of 0.1 mA, where the nominal current is adjustable between 5 A and 1 A. Harmonic measurement is carried out up to the 127th harmonic, enabling detailed analysis of power quality. Additionally, 4 multifunction inputs are integrated, which can be configured as differential current inputs, temperature inputs, or additional current inputs depending on the setup. This flexibility extends the device’s application possibilities in complex installations.
Technology Explained Simply
The integrated data storage with 4 GB of memory enables long-term recording of measurement values, which is necessary for analyzing consumption patterns, load profiles, or disturbances. The device’s peripherals include 4 digital inputs, 4 digital outputs, and one analog output, which can be used for controlling and monitoring external components. Two Ethernet ports (RJ45) enable network integration and data access via IP-based protocols. The OPC UA interface supports integration into higher-level energy management systems and enables communication with other devices and controls in an Industry 4.0 environment.
Compatibility and Accessories
The base unit is modular and can be expanded with additional modules to adapt functionality to specific requirements. The delivery includes the installation manual including safety instructions (item 33.03.376), a pre-installed bus connector for the base unit (item 52.31.205), and an end angle (item 10.01.953) for mechanical termination of the DIN rail mounting. The programming software 'GridVis Essential' is available via the Janitza website and is used for configuration, visualization, and evaluation of measurement data.
Mounting and Installation
Mounting is performed on a DIN rail, with the device secured using integrated retaining clips and the supplied end angle. Electrical connections are made via designated terminal blocks for voltage, current, and peripherals. Installation requires knowledge in electrical engineering and compliance with the safety instructions specified in the installation manual.
Operational Advantages
The UMG 801 base unit offers high measurement accuracy and comprehensive data acquisition, which is essential for optimizing energy consumption, fault diagnosis, and compliance with energy efficiency standards. The modular design allows for step-by-step expansion of functionality, optimizing acquisition costs. The OPC UA interface and network capability facilitate integration into existing IT and automation systems, improving data availability and analysis. The integrated storage of measurement data enables retrospective analysis without external storage media.