Further information for ifm Electronic TD2233 temperature transmitter Pt1000
Accuracy / Deviations
Accuracy of analogue output
± 0,3 + (± 0,1 % MS) K
Temperature coefficient
0.1; (Deviation from reference condition 25 °C) % of span / 10 K
Approvals / tests
EMC
DIN EN 61000-6-2; DIN EN 61000-6-3
Shock resistance
DIN IEC 68-2-27 / 50 g (11 ms)
Vibration resistance
DIN IEC 68-2-6 / 10 g (10...2000 Hz)
MTTF
407 years
Note on approval
Factory certificate available for download at www.factory-certificate.ifm
UL approval
UL approval number UL / K001
Displays / controls
Indication
7-segment LED display, 4-digit; Display unit / status, °C / °F
Electrical connection
Plug connection
1 x M12; coding: A; contacts: 4
Electrical data
Operating voltage
18...32 DC; ("supply class 2" according to cULus) V
Electricity consumption
< 50 mA
Protection class
III
Standby delay time
2 s
Reverse polarity protection
Environmental conditions
Ambient temperature
-25...80 °C
Storage temperature
-40...100 °C
Degree of protection
IP 67; IP 68; IP 69K
Field of application
Measuring element
1 x Pt 1000; (according to DIN EN 60751, Class A)
Media
Liquid and gaseous media
Compressive strength
160 bar / 16 MPa
Vacuum tightness
-1000 mbar / -0.1 MPa
Interfaces
Transmission type
COM2 (38.4 kBaud)
IO-Link revision
1.1
Profiles
Smart Sensor - SSP 0 / Generic Profiled Sensor
Min. process cycle time
2,3 ms
Supported DeviceIDs
Operation mode / DeviceID; default / 376
Measurement / adjustment range
Factory setting
0...300 °F
Analog output resolution
0,04 K
Display resolution
0,28 K
Mechanical data
Housing
Cylindrical
Dimensions
Ø 6 / L = 148 mm
Materials
1.4404 (stainless steel / 316L); PEI; FKM
Materials in contact with the medium
1.4404 (stainless steel / 316L) electropolished
Surface roughness Ra/Rz of medium-contacting surfaces
Ra < 0,8 µm
Rod diameter
6 mm
Outputs
Total number of outputs
1
Output signal
Analogue signal; IO-Link; (configurable)
Number of analogue outputs
1
Analog output current
4...20 mA
Max. load
300 Ω
Short-circuit protection
Overload resistant
Product features
Number of inputs and outputs
Number of analog outputs: 1
Measuring range
-50...150 °C / -58...302 °F
Communication interface
IO-Link
Process connection
Terminal adaptation Ø 6 mm
Installation length EL
100 mm
Remarks
Remarks
MS = set measurement range; Accuracy values apply to moving water.
Response times
Response dynamics T05 / T09
1 / 3 s
Temperaturtransmitter, 1 x Pt 1000, (nach DIN EN 60751, Klasse A), Analogsignal, IO-Link, Einbaulänge EL 100 mm, Messbereich -50...150 °C, -58...302 °F, Werkseinstellung 0...300 °F, Druckfestigkeit 160 bar, Klemmadaption Ø 6 mm, M12 Steckverbindung