| Accuracy / Deviations |
| Switching point accuracy | < ± 0.4; (turn down 1:1) % of span |
| Repeatability | < ± 0.1; (at temperature variations < 10 K; Turn down 1:1) % of span |
| Characteristic deviation | < ± 1; (linearity, including hysteresis and repeatability; limit point setting according to DIN EN IEC 62828-1) % of span |
| Hysteresis deviation | < ± 0.1; (Turn down 1:1) % of span |
| Long-term stability | < ± 0.05; (turn down 1:1; per 6 months) % of span |
| Temperature coefficient zero point | 0.2; (5...80 °C) % of span / 10 K |
| Temperature coefficient range | 0.2; (5...80 °C) % of span / 10 K |
| Approvals / tests |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Shock resistance | DIN EN 60068-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6 / 10 g (10...2000 Hz) |
| MTTF | 143 years |
| Displays / controls |
| Indication | display unit / 3 x LED, green (bar, psi, MPa); switching state / 2 x LED, yellow; measured values / alphanumeric display, red / green 4-digit |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 18...30 DC; (according to SELV/PELV) V |
| Electricity consumption | < 35 mA |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Standby delay time | 0,3 s |
| Reverse polarity protection | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | 5...80 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 67 |
| Field of application |
| Special feature | Gold-plated contacts |
| Measuring element | pressure transmitter |
| Application | Flush-mounted for food and beverage industry |
| Media | Liquid and gaseous media |
| Medium temperature | 5...125; (150 maximum 1h) °C |
| Min. bursting pressure | 1200 bar / 17400 psi / 120 MPa |
| Compressive strength | 800 bar / 11580 psi / 80 MPa |
| Vacuum tightness | -1000 mbar / -0.1 MPa |
| Pressure type | Gauge pressure |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 0 / Generic Profiled Sensor; Function / Device identification; Function / Process data variable; Function / Device diagnosis |
| Required master port class | A |
| Analog process data | 1 |
| Process data binary | 2 |
| Min. process cycle time | 2,3 ms |
| Supported DeviceIDs | Operating mode / DeviceID; default / 458 |
| SIO mode | |
| Measurement / adjustment range |
| Switching point SP | 4...600 bar / 60...8700 psi / 0.4...60 MPa |
| Reverse switch point rP | 1...597 bar / 20...8660 psi / 0.1...59.7 MPa |
| Analog start point | 0...480 bar / 0...6960 psi / 0...48 MPa |
| Analog endpoint | 120...600 bar / 1740...8700 psi / 12...60 MPa |
| In steps of | 1 bar / 20 psi / 0.1 MPa |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 34 / L = 151 mm |
| Materials | 1.4542 (stainless steel / 17-4 PH / 630); 1.4404 (stainless steel / 316L); 1.4435 (stainless steel / 316L); PBT+PC-GF30; PBT-GF20; PC |
| Materials in contact with the medium | 1.4435 (stainless steel / 316L) |
| Min. pressure cycles | 60 million; (at 1.2 times rated pressure) |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; analog signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2 V |
| Continuous current rating of switching output DC | 250 mA |
| Switching frequency DC | < 500 Hz |
| Number of analogue outputs | 1 |
| Analog output current | 4...20; (scalable 1:5) mA |
| Max. load | 500 Ω |
| Analog output voltage | 0...10; (scalable 1:5) V |
| Minimum load resistance | 2000 Ω |
| Short-circuit protection type | timed |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
| Measuring range | 0...600 bar / 0...8700 psi / 0...60 MPa |
| Process connection | Homogenizer connection |
| Response times |
| Response time | < 1,5 ms |
| Adjustable delay time dS, dr | 0...50 s |
| Process value damping dAP | 0...4 s |
| Attenuation analog output dAA | 0...4 s |
| Max. rise time analog output | 3 ms |
| Software / Programming |
| Parameterization options | Hysteresis / window; normally open contact (NO) / normally closed contact (NC); switching / reset delay; damping; display unit; current / voltage output |
Drucksensor für Homogenisierer, 0...600 bar, 0...8700 psi, 0...60 MPa, Homogenisierer-Anschluss, Schaltsignal, Analogsignal, IO-Link, 4...20, (skalierbar 1:5) mA, 0...10, (skalierbar 1:5) V, Steckverbindung, 5...125, (150 maximal 1h) °C, IP 67, Relativdruck