| Accuracy / Deviations |
| Switching point accuracy | < ± 0.5 (according to DIN EN 61298-2) % of span |
| Repeatability | < ± 0.05; (with temperature variations < 10 K) % of span |
| Characteristic deviation | < ± 0.5; (linearity including hysteresis and repeatability, end-point setting according to DIN EN IEC 62828-1) % of span |
| Linearity deviation | < ± 0.1 (BFSL) / < ± 0.2 (LS) % of span |
| Neutral point stabilisation | IO-Link / 1.0; (See operating manual for zero point behavior); Switching output / 1.0 % of range |
| Hysteresis deviation | < ± 0.2 % of span |
| Long-term stability | < ± 0.1; (per 6 months) % of span |
| Temperature coefficient zero point | < 0.1 (-25...90 °C) / < 0.2 (-40...-25 °C) % of span / 10 K |
| Temperature coefficient range | < 0.1 (-25...90 °C) / < 0.2 (-40...-25 °C) % of span / 10 K |
| Approvals / tests |
| EMC | DIN EN 61326-1 |
| Shock resistance | DIN EN 60068-2-27 / 500 g (1 ms) |
| Vibration resistance | DIN EN 60068-2-6 / 20 g (10...2000 Hz) |
| MTTF | 668 years |
| UL approval | Approval number UL / J016 |
| Printer directive | Good engineering practice; suitable for fluids of group 2; fluids of group 1 on request |
| Electrical connection |
| Plug connection | 1 x M12; coding: A; contacts: 4 |
| Electrical data |
| Operating voltage | 18...30 DC V |
| Electricity consumption | < 15 mA |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Standby delay time | < 0,3 s |
| Reverse polarity protection | |
| Environmental conditions |
| Ambient temperature | -40...90 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 67; IP 69K |
| Field of application |
| Measuring element | metallic thin-film cell |
| Application | for industrial use |
| Media | Liquid and gaseous media |
| Medium temperature | -40...90 °C |
| Min. bursting pressure | 120 MPa |
| Compressive strength | 62.5 MPa |
| Note on pressure resistance | Static |
| Vacuum tightness | -1000 mbar / -0.1 MPa |
| Pressure type | Gauge pressure |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 0 / Generic Profiled Sensor; Function / Device identification; Function / Process data variable; Function / Device diagnosis |
| Required master port class | A |
| Min. process cycle time | 5 ms |
| Supported DeviceIDs | Operating mode / DeviceID; default / 781 |
| SIO mode | |
| Measurement / adjustment range |
| Switching point SP | 0.25...25 MPa |
| Reverse switch point rP | 0.13...24.88 MPa |
| In steps of | 0.01 MPa |
| Factory setting | SP1 = 6.25 MPa / rP1 = 5.75 MPa / ou1 = Hno;; SP2 = 18.75 MPa / rP2 = 18.25 MPa / ou2 = Hno;; dS1/dS2 = 0 ms / dr1/dr2 = 0 ms; coF = 0 % / P-n = PnP / dAP= 60 ms |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 19 / L = 67 mm |
| Materials | 1.4542 (stainless steel / 17-4 PH / 630); 1.4404 (stainless steel / 316L); PEI |
| Materials in contact with the medium | 1.4305 (Stainless steel / 303); 1.4542 (Stainless steel / 17-4 PH / 630) |
| Min. pressure cycles | 60 million; (at 1.2 times rated pressure) |
| Tightening moment | 50; (recommended torque; dependent on lubrication, sealing and pressure load) Nm |
| Choke element present | |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2 V |
| Continuous current rating of switching output DC | 100 mA |
| Switching frequency DC | < 170 Hz |
| Short-circuit protection type | timed |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range | 0...25 MPa |
| Process connection | Threaded connection R 1/4 external thread internal thread: M5 |
| Remarks |
| Remarks | BFSL = Best Fit Straight Line (minimum setting); LS = limit point setting |
| Response times |
| Response time | < 3 ms |
| Software / Programming |
| Parameterization options | Hysteresis / window; Normally open contact (NO) / Normally closed contact (NC); Switching logic; Switching / reset delay; Damping |
Elektronischer Druckschalter, 0...25 MPa, R 1/4 Außengewinde, Schaltsignal, IO-Link, Steckverbindung, -40...90 °C, IP 67, IP 69K, Relativdruck