| Accuracy / Deviations |
| Switching point accuracy | < ± 0.5 % of span |
| Repeatability | < ± 0.1; (with temperature variations < 10 K) % of span |
| Characteristic deviation | < ± 0.25 (BFSL) / < ± 0.5 (LS); (BFSL = Best Fit Straight Line (minimum setting); LS = end-point setting) % of span |
| Hysteresis deviation | < ± 0.25 % of span |
| Long-term stability | < ± 0.05; (per 6 months) % of span |
| Temperature coefficient zero point | < ± 0.2; (-0...80 °C) % of span / 10 K |
| Temperature coefficient range | < ± 0.2; (-0...80 °C) % of span / 10 K |
| Approvals / tests |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Shock resistance | DIN EN 60068-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6 / 20 g (10...2000 Hz) |
| MTTF | 260 years |
| UL approval | UL certification number / J001 |
| Printer directive | Good engineering practice; suitable for fluids of group 2; fluids of group 1 on request |
| Displays / controls |
| Indication | display unit / 3 x LED, green (bar, psi, MPa); switching state / 2 x LED, yellow; measured values / alphanumeric display, red / green 4-digit |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 18...30 DC; (according to SELV/PELV) V |
| Electricity consumption | < 35 mA |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Standby delay time | < 0,3 s |
| Reverse polarity protection | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...80 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 65; IP 67 |
| Field of application |
| Special feature | Gold-plated contacts |
| Measuring element | Ceramic-capacitive pressure sensor cell |
| Application | for industrial use |
| Media | Liquid and gaseous media |
| Medium temperature | -25...80 °C |
| Min. bursting pressure | 150 bar / 2175 psi / 15 MPa |
| Compressive strength | 75 bar / 1087 psi / 7.5 MPa |
| Vacuum tightness | -1000 mbar / -0.1 MPa |
| Pressure type | Relative pressure; vacuum |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Required master port class | A; (if PIN 2 not connected: B) |
| Analog process data | 1 |
| Process data binary | 2 |
| Supported DeviceIDs | Operating mode / DeviceID; Factory setting / CMPT = 2 / 403; Status_B High Resolution / CMPT = 3 / 601 |
| Note | Further information can be found in the IODD-PDF file under "Downloads" |
| Profiles | Smart Sensor - SSP 0 / Generic Profiled Sensor; Function / Device identification; Function / Process data variable; Function / Device diagnosis |
| Min. process cycle time | 2,3 ms |
| IO-Link pressure resolution | 0.01 bar / 0.001 MPa |
| IO-Link process data (cyclic) | Function / bit length; pressure / 14; binary switching information / 2 |
| IO-Link functions (asynchronous) | Application-specific marking |
| SIO mode | |
| Measurement / adjustment range |
| Switching point SP | -0.9...10 bar / -13.5...145 psi / -0.09...1 MPa |
| Reverse switch point rP | -0.95...9.95 bar / -14...144.5 psi / -0.095...0.995 MPa |
| Min. distance between SP and rP | 0.05 bar / 1 psi / 0.005 MPa |
| In steps of | 0.05 bar / 0.5 psi / 0.005 MPa |
| Mechanical data |
| Materials | 1.4404 (stainless steel / 316L); PBT+PC-GF30; PBT-GF20; PC |
| Materials in contact with the medium | 1.4404 (stainless steel / 316L); ceramic; FKM |
| Min. pressure cycles | 100 million |
| Tightening moment | 25...35; (recommended torque; dependent on lubrication, seal and pressure load) Nm |
| Choke element present | no (retrofit available) |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2,5 V |
| Continuous current rating of switching output DC | 150; (200 (...60 °C) 250 (...40 °C)) mA |
| Switching frequency DC | < 170 Hz |
| Short-circuit protection type | timed |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range | -1...10 bar / -14.5...145 psi / -100...1000 kPa / -0.1...1 MPa |
| Process connection | Threaded connection G 1/4 male thread; Internal thread: M5 |
| Response times |
| Response time | < 3 ms |
| Adjustable delay time dS, dr | 0...50 s |
| Software / Programming |
| Parameterization options | Hysteresis / window; Normally open contact (NO) / Normally closed contact (NC); Switching logic; Switching / reset delay; Damping; Display unit |
Electronic pressure switch, -1...10 bar, -14.5...145 psi, -100...1000 kpa, -0.1...1 MPa, G 1/4 external thread, switching signal, IO-Link, (configurable), plug connection, -25...80 °C, IP 65, IP 67, relative pressure, vacuum