| Accuracy / Deviations |
| Switching point accuracy | < ± 1.0 % of span |
| Repeatability | < ± 0.1; (with temperature variations < 10 K) % of span |
| Linearity deviation | < ± 0.5 % of span |
| Hysteresis deviation | < ± 0.1 % of span |
| Long-term stability | < ± 0.1; (per year) % of span |
| Temperature coefficient zero point | < ± 0.2; (-25...80 °C) % of span / 10 K |
| Temperature coefficient range | < ± 0.3; (-25...80 °C) % of span / 10 K |
| Approvals / tests |
| EMC | EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 Radiated HF / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-6 Conducted HF / 10 V |
| Shock resistance | DIN IEC 68-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN IEC 68-2-6 / 20 g (10...2000 Hz) |
| MTTF | 225 years |
| Printer directive | Good engineering practice; suitable for fluids of group 2; fluids of group 1 on request |
| Displays / controls |
| Indication | Switching state / LED, red; Function indicator / 7-segment LED display; Measured values / 7-segment LED display |
| Electrical connection |
| Required fuse rating | Miniature fuse according to IEC60127-2 Sheet 1; ≤ 5 A; fast |
| Plug connection | 1 x 1/2"; coding: C; contacts: 5 |
| Electrical data |
| Operating voltage tolerance | 5...10 % |
| Operating voltage | 90...250 AC V |
| Nominal voltage AC | < 250 V |
| Electricity consumption | < 10 mA |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | II |
| Standby delay time | 0,2 s |
| Reverse polarity protected | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...80 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 65 |
| Field of application |
| Application | for industrial use |
| Media | Liquid and gaseous media |
| Medium temperature | -25...80 °C |
| Min. bursting pressure | 50 bar / 1476 inHg / 5000 kPa |
| Compressive strength | 20 bar / 590 inHg / 2000 kPa |
| Pressure type | Relative pressure; vacuum |
| Measurement / adjustment range |
| Switching point SP | -0.97...1 bar / -29...30 inHg / -97...100 kPa |
| Reverse switch point rP | -0.99...0.98 bar / -30...29 inHg / -99...98 kPa |
| In steps of | 0.01 bar / 1 inHg / 1 kPa |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 34 / L = 120 mm |
| Materials | 1.4301 (stainless steel / 304); PC; PBT; PA; FKM |
| Materials in contact with the medium | 1.4305 (stainless steel / 303); ceramic; FKM |
| Min. pressure cycles | 100 million |
| Choke element present | no (retrofit available) |
| Outputs |
| Total number of outputs | 1 |
| Output signal | Switching signal |
| Electrical version | Triac |
| Number of digital outputs | 1 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output AC | 2 V |
| Continuous current rating of switching output AC | 250; ((...70 °C) 1000 (...60 °C) 1500 (...45 °C) 2500 (...20 °C)) mA |
| Switching frequency AC | < 160 Hz |
| Short-circuit-proof | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 1 |
| Measuring range | -1...1 bar / -1000...1000 mbar / -30...30 inHg / -100...100 kPa |
| Process connection | Threaded connection 1/4" NPT internal thread |
| Remarks |
| Remarks | n.c. = not assigned |
| Response times |
| Adjustable delay time dS, dr | 0, 0,2,...10, 11,...50 s |
| Process value damping dAP | 0...4 s |
| Software / Programming |
| Switching point adjustment | Programming button |
| Parameterization options | Hysteresis / window; normally open contact (NO) / normally closed contact (NC); pull-in/drop-out delay; damping; display value adjustment; rotatable / switchable display; display unit |
Elektronischer Druckschalter, -1...1 bar, -1000...1000 mbar, -30...30 inhg, -100...100 kpa, 1/4' NPT Innengewinde, Schaltsignal, Steckverbindung, -25...80 °C, IP 65, Relativdruck, Vakuum