| Accuracy / Deviations |
| Switching point accuracy | < ± 0.4; (turn down 1:1) % of span |
| Repeatability | < ± 0.1; (at temperature variations < 10 K; Turn down 1:1) % of span |
| Characteristic deviation | < ± 0.25 (BFSL) / < ± 0.5 (LS); (turn down 1:1; BFSL = Best Fit Straight Line (minimum setting); LS = endpoint setting) % of span |
| Hysteresis deviation | < ± 0.1; (Turn down 1:1) % of span |
| Long-term stability | < ± 0.1; (turn down 1:1; per year) % of span |
| Temperature coefficient zero point | < ± 0.2; (0...80 °C) % of span / 10 K |
| Temperature coefficient range | < ± 0.2; (0...80 °C) % of span / 10 K |
| Approvals / tests |
| EMC | EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 Radiated HF / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-5 Surge / 0.5/1 kV; EN 61000-4-6 Conducted HF / 10 V |
| Shock resistance | DIN IEC 68-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN IEC 68-2-6 / 20 g (10...2000 Hz) |
| MTTF | 131 years |
| Printer directive | Good engineering practice; suitable for fluids of group 2; fluids of group 1 on request |
| Displays / controls |
| Indication | Display unit / 3 x LED, green; Switching state / 2 x LED, yellow; Function indication / alphanumeric display, 4-digit; Measurement values / alphanumeric display, 4-digit |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 18...32 DC; (according to SELV/PELV) V |
| Electricity consumption | < 35 mA |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Standby delay time | 0,3 s |
| Reverse polarity protection | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...80 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 67 |
| Field of application |
| Special feature | Gold-plated contacts |
| Application | for industrial use |
| Media | Liquid and gaseous media |
| Conditionally suitable for | Use in gaseous media at pressures > 25 bar only on request |
| Medium temperature | -25...80 °C |
| Min. bursting pressure | 850 bar / 12300 psi / 85 MPa |
| Compressive strength | 400 bar / 5800 psi / 40 MPa |
| Pressure type | Gauge pressure |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.0 |
| Min. process cycle time | 2,3 ms |
| Supported DeviceIDs | Operating mode / DeviceID; default / 67 |
| Measurement / adjustment range |
| Switching point SP | 2...250 bar / 30...3625 psi / 0.2...25 MPa |
| Reverse switch point rP | 1...249 bar / 15...3610 psi / 0.1...24.9 MPa |
| Analog start point | 0...187.5 bar / 0...2720 psi / 0...18.75 MPa |
| Analog endpoint | 62.5...250 bar / 905...3625 psi / 6.25...25 MPa |
| In steps of | 0.5 bar / 5 psi / 0.05 MPa |
| Factory setting | SP1 = 905 psi / rP1 = 835 psi; SP2 = 2720 psi / rP2 = 26450 psi; ASP = 0 psi / AEP = 3525 psi |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 34 / L = 91,5 mm |
| Materials | 1.4301 (stainless steel / 304); 1.4404 (stainless steel / 316L); PC; PBT; PEI; FKM |
| Materials in contact with the medium | 1.4305 (stainless steel / 303); ceramic; FKM |
| Min. pressure cycles | 100 million |
| Choke element present | |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; analog signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2 V |
| Continuous current rating of switching output DC | 250 mA |
| Switching frequency DC | < 500 Hz |
| Number of analogue outputs | 1 |
| Analog output current | 4...20; (scalable 1:4) mA |
| Max. load | (Ub - 10 V) / 20 mA Ω |
| Analog output voltage | 0...10; (scalable 1:4) V |
| Minimum load resistance | 2000 Ω |
| Short-circuit protection type | timed |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
| Measuring range | 0...250 bar / 0...3630 psi / 0...25 MPa |
| Process connection | Threaded connection 1/4" NPT internal thread |
| Response times |
| Response time | < 1,5 ms |
| Process value damping dAP | 0,01...4 s |
| Attenuation analog output dAA | 0,01...4 s |
| Max. rise time analog output | 3 ms |
| Software / Programming |
| Parameterization options | Hysteresis / window; Normally open contact (NO) / Normally closed contact (NC); Switching logic; Current/voltage output; Damping; Display value adjustment; Rotatable / switchable display; Display unit; Zero point; Range |
Elektronischer Drucksensor, 0...250 bar, 0...3630 psi, 0...25 MPa, 1/10,2 cm ( 4 inch ) NPT Innengewinde, Schaltsignal, Analogsignal, IO-Link, 4...20, (skalierbar 1:4) mA, 0...10, (skalierbar 1:4) V, Steckverbindung, -25...80 °C, IP 67, Relativdruck