| Accuracy / Deviations |
| Switching point accuracy | < ± 0.4; (turn down 1:1) % of span |
| Repeatability | < ± 0.1; (at temperature variations < 10 K; Turn down 1:1) % of span |
| Characteristic deviation | < ± 0.25 (BFSL) / < ± 0.5 (LS); (turn down 1:1; BFSL = Best Fit Straight Line (minimum setting); LS = endpoint setting) % of span |
| Hysteresis deviation | < ± 0.1; (Turn down 1:1) % of span |
| Long-term stability | < ± 0.05; (turn down 1:1; per 6 months) % of span |
| Temperature coefficient zero point | < ± 0.2; (-0...80 °C) % of span / 10 K |
| Temperature coefficient range | < ± 0.2; (-0...80 °C) % of span / 10 K |
| Notes on accuracy / deviation | Switching point accuracy, characteristic curve deviation under DNVGL: < ± 1% |
| Approvals / tests |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Shock resistance | DIN EN 60068-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6 / 20 g (10...2000 Hz) |
| MTTF | 138 years |
| UL approval | approval number UL / J012 |
| Printer directive | Good engineering practice; suitable for fluids of group 2; fluids of group 1 on request |
| Displays / controls |
| Indication | Display unit / 3 x LED, green (bar, psi, kPa); Switching state / 2 x LED, yellow; Measured values / alphanumeric display, red / green 4-digit |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 18...30 DC; (according to SELV/PELV) V |
| Electricity consumption | < 35 mA |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Standby delay time | 0,3 s |
| Reverse polarity protection | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...80 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 65; IP 67 |
| Field of application |
| Special feature | Gold-plated contacts |
| Measuring element | Ceramic-capacitive pressure sensor cell |
| Application | for industrial use |
| Media | Liquid and gaseous media |
| Medium temperature | -25...80 °C |
| Min. bursting pressure | 50 bar / 725 psi / 5000 kPa |
| Compressive strength | 20 bar / 290 psi / 2000 kPa |
| Vacuum tightness | -1000 mbar / -0.1 MPa |
| Pressure type | Gauge pressure |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Required master port class | A; (if PIN 2 not connected: B) |
| Supported DeviceIDs | Operation / DeviceID; Factory setting / CMPT = 2 / 464; Status_B High Resolution / CMPT = 3 / 975 |
| Note | Further information can be found in the IODD-PDF file under "Downloads" |
| Profiles | Smart Sensor - SSP 0 / Generic Profiled Sensor; Function / Device identification; Function / Process data variable; Function / Device diagnosis |
| Min. process cycle time | 2,3 ms |
| IO-Link pressure resolution | 0.005 bar |
| IO-Link process data (cyclic) | Function / bit length; pressure / 14; binary switching information / 2 |
| IO-Link functions (asynchronous) | Application-specific marking |
| SIO mode | |
| Measurement / adjustment range |
| Analog start point | -0.125...2 bar / -1.8...29 psi / -12.5...200 kPa |
| Analog endpoint | 0.375...2.5 bar / 5.45...36.25 psi / 37.5...250 kPa |
| Switching point SP | -0.11...2.5 bar / -1.6...36.25 psi / -11...250 kPa |
| Reverse switch point rP | -0.12...2.49 bar / -1.75...36.1 psi / -12...249 kPa |
| Min. distance between SP and rP | 0.015 bar / 0.15 psi / 1.5 kPa |
| In steps of | 0.005 bar / 0.05 psi / 0.5 kPa |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 34 / L = 90,7 mm |
| Materials | 1.4404 (stainless steel / 316L); PBT+PC-GF30; PBT-GF20; PC |
| Materials in contact with the medium | 1.4404 (stainless steel / 316L); Al2O3 (96 %; ceramic); FKM |
| Min. pressure cycles | 100 million |
| Tightening moment | 25...35; (recommended torque; dependent on lubrication, seal and pressure load) Nm |
| Choke element present | no (retrofit available) |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; analog signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2 V |
| Continuous current rating of switching output DC | 250 mA |
| Switching frequency DC | < 500 Hz |
| Number of analogue outputs | 1 |
| Analog output current | 4...20; (scalable 1:5) mA |
| Max. load | 500 Ω |
| Analog output voltage | 0...10; (scalable 1:5) V |
| Minimum load resistance | 2000 Ω |
| Short-circuit protection type | timed |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
| Measuring range | -0.125...2.5 bar / -125...2500 mbar / -1.8...36.25 psi / -12.5...250 kPa |
| Process connection | threaded connection G 1/4 internal thread |
| Response times |
| Response time | < 1,5 ms |
| Adjustable delay time dS, dr | 0...50 s |
| Process value damping dAP | 0...4 s |
| Attenuation analog output dAA | 0...4 s |
| Max. rise time analog output | 3 ms |
| Software / Programming |
| Parameterization options | Hysteresis / window; normally open contact (NO) / normally closed contact (NC); switching / reset delay; damping; display unit; current / voltage output |