| Accuracy / Deviations |
| Switching point accuracy | < ± 0.5 % of span |
| Repeatability | < ± 0.1; (with temperature variations < 10 K) % of span |
| Characteristic deviation | < ± 0.25 (BFSL) / < ± 0.5 (LS); (BFSL = Best Fit Straight Line (minimum setting); LS = end-point setting) % of span |
| Hysteresis deviation | < ± 0.25 % of span |
| Long-term stability | < ± 0.05; (per 6 months) % of span |
| Temperature coefficient zero point | 0.2; (0...60 °C) % of range / 10 K |
| Temperature coefficient range | 0.2; (0...60 °C) % of range / 10 K |
| Approvals / tests |
| ATEX equipment marking | II 3D Ex tc IIIC T80°C Dc X |
| EMC | EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 Radiated HF / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-5 Surge / 0.5/1 kV; EN 61000-4-6 Conducted HF / 10 V |
| Shock resistance | DIN IEC 68-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN IEC 68-2-6 / 20 g (10...2000 Hz) |
| MTTF | 194 years |
| Printer directive | Good engineering practice; suitable for fluids of group 2; fluids of group 1 on request |
| Displays / controls |
| Indication | Display unit / 3 x LED, green; Switching state / 2 x LED, yellow; Function indication / alphanumeric display, 4-digit; Measurement values / alphanumeric display, 4-digit |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 18...36 DC; (according to SELV/PELV) V |
| Electricity consumption | < 50 mA |
| Protection class | III |
| Over voltage protection | ja; (< 40 V) |
| Standby delay time | 0,3 s |
| Reverse polarity protection | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -20...60 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 65 |
| Field of application |
| Special feature | Gold-plated contacts |
| Application | for industrial use |
| Media | Liquid and gaseous media |
| Medium temperature | -20...60 °C |
| Min. bursting pressure | 50 bar / 725 psi / 5000 kPa |
| Compressive strength | 20 bar / 290 psi / 2000 kPa |
| Pressure type | Gauge pressure |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 CDV |
| Required master port class | A |
| Analog process data | 1 |
| Process data binary | 2 |
| Min. process cycle time | 2,3 ms |
| Supported DeviceIDs | Operation mode / DeviceID; default / 312 |
| SIO mode | |
| Measurement / adjustment range |
| Switching point SP | 0.02...2.5 bar / 0.4...36.2 psi / 2...250 kPa |
| Reverse switch point rP | 0.01...2.49 bar / 0.2...36 psi / 1...249 kPa |
| In steps of | 0.01 bar / 0.2 psi / 1 kPa |
| Factory setting | SP1 = 0.63 bar / rP1 = 0.58 bar; SP2 = 1.88 bar / rP2 = 1.83 bar |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 36 / L = 94 mm |
| Materials | 1.4301 (stainless steel / 304); 1.4404 (stainless steel / 316L); PC; PBT; PEI; FKM; PTFE |
| Materials in contact with the medium | 1.4305 (stainless steel / 303); ceramic; FKM |
| Min. pressure cycles | 100 million |
| Choke element present | no (retrofit available) |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2 V |
| Continuous current rating of switching output DC | 250 mA |
| Switching frequency DC | < 170 Hz |
| Short-circuit protection type | timed |
| Short-circuit protection | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range | 0...2.5 bar / 0...2500 mbar / 0...36.3 psi / 0...250 kPa |
| Process connection | threaded connection G 1/4 internal thread |
| Response times |
| Adjustable delay time dS, dr | 0; 0,2...50 s |
| Software / Programming |
| Parameterization options | Hysteresis / window; Normally open contact (NO) / Normally closed contact (NC); Diagnostic function; Switching logic; On/off delay; Damping; Display unit |
Elektronischer Druckschalter, 0...2,5 bar, 0...2500 mbar, 0...36,3 psi, 0...250 kpa, G 1/4 Innengewinde, Schaltsignal, IO-Link, Steckverbindung, -20...60 °C, IP 65, Relativdruck