| Accuracy / Deviations |
| Switching point accuracy | < ± 0.5; (Turn down 1:1) % of span |
| Repeatability | < ± 0.1; (at temperature variations < 10 K; Turn down 1:1) % of span |
| Characteristic deviation | < ± 0.5; (Turn down 1:1, linearity, including hysteresis and repeatability, end-point setting according to DIN EN IEC 62828-1) % of span |
| Linearity deviation | < ± 0.25; (turn down 1:1) % of span |
| Hysteresis deviation | < ± 0.2; (Turn down 1:1) % of span |
| Long-term stability | < ± 0.1; (turn down 1:1; per year) % of span |
| Temperature coefficient zero point | < ± 0.1; (0...70 °C) % of span / 10 K |
| Temperature coefficient range | < ± 0.2; (0...70 °C) % of span / 10 K |
| Approvals / tests |
| EMC | EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 Radiated HF / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-5 Surge / 0.5/1 kV; EN 61000-4-6 Conducted HF / 10 V |
| Shock resistance | DIN IEC 68-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN IEC 68-2-6 / 20 g (10...2000 Hz) |
| MTTF | 160 years |
| Note on approval | Factory certificate available for download at www.factory-certificate.ifm |
| UL approval | UL approval number / J018; UL file number / E174189 |
| Displays / controls |
| Indication | Display unit / LED, green; Switching state / LED, yellow; Function indicator / alphanumeric display, 4-digit; Measured values / alphanumeric display, 4-digit |
| Display unit | mbar; kPa; inH2O; mmWS; % of range |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Operating voltage | 20...32 DC V |
| Electricity consumption | 3,6...21 mA |
| Standby delay time | 1 s |
| Reverse polarity protection | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...80 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 67; IP 68; IP 69K |
| Field of application |
| Special feature | Gold-plated contacts |
| Application | Flush-mounted for food and beverage industry |
| Media | Paste and solid-containing media; Liquid and gaseous media |
| Medium temperature | -25...125; (145 max. 1h) °C |
| Min. bursting pressure | 30000 mbar / 12044 inH2O / 3000 kPa |
| Compressive strength | 4000 mbar / 1606 inH2O / 400 kPa |
| Vacuum tightness | -1000 mbar / -0.1 MPa |
| Pressure type | Gauge pressure |
| MAWP for applications according to CRN | 4 bar |
| Backlash-free | |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.0 |
| Required master port class | A |
| Analog process data | 1 |
| Process data binary | 2 |
| Min. process cycle time | 2,3 ms |
| Supported DeviceIDs | Operation / DeviceID; default / 259 |
| SIO mode | |
| Measurement / adjustment range |
| Switching point SP | -4.8...100 mbar / -1.92...40.16 inH2O / -0.48...10 kPa |
| Reverse switch point rP | -5...99.8 mbar / -2...40.08 inH2O / -0.5...9.98 kPa |
| Analog start point | -5...75 mbar / -2...30.12 inH2O / -0.5...7.5 kPa |
| Analog endpoint | 20...100 mbar / 8.04...40.16 inH2O / 2...10 kPa |
| In steps of | 0.1 mbar / 0.04 inH2O / 0.01 kPa |
| Factory setting | SP1 = 25 mbar / rP1 = 23 mbar; SP2 = 75 mbar / rP2 = 73 mbar; ASP = 0 mbar / AEP = 100 mbar; dAP = 0.06 s / dAA = 0.03 s |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 50 / L = 105,8 mm |
| Materials | 1.4404 (Stainless steel / 316L); FKM; PTFE; PBT; PEI; PFA |
| Materials in contact with the medium | Ceramic (99.9 % Al2O3); 1.4435 (stainless steel / 316L) surface finish: Ra < 0.4 µm / Rz = 4 µm; PTFE |
| Min. pressure cycles | 100 million |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; analog signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Number of analogue outputs | 1 |
| Analog output current | 4...20, reversible; (scalable) mA |
| Short-circuit protection type | timed |
| Max. load | 300 Ω |
| Max. voltage drop switching output DC | 2 V |
| Continuous current rating of switching output DC | 250 mA |
| Switching frequency DC | 125 Hz |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
| Measuring range | -0.005...0.1 bar / -5...100 mbar / -2...40.16 inH2O / -0.5...10 kPa |
| Process connection | Threaded connection G 1 external thread with sealing contour Aseptoflex Vario |
| Note | G1 thread according to ISO 228. Alternatively, sealing via rear sealing contour with gasket in accordance with DIN EN ISO 1179-2. |
| Response times |
| Process value damping dAP | 0...30 s |
| Attenuation analog output dAA | 0,01...99,99 s |
| Step response time analog output | 45 ms |
| Min. response time relay output dAP | 3 ms |