| Accuracy / Deviations |
| Switching point accuracy | < ± 0.2; (Turn down 1:1) % of span |
| Repeatability | < ± 0.1; (at temperature variations < 10 K; Turn down 1:1) % of span |
| Characteristic deviation | < ± 0.2; (Turn down 1:1, linearity, including hysteresis and repeatability, setpoint adjustment according to DIN EN IEC 62828-1) % of span |
| Linearity deviation | < ± 0.15; (turn down 1:1) % of span |
| Neutral point stabilisation | IO-Link, Analog output / 0.15; Display, Switch output / 0.2 % of range |
| Hysteresis deviation | < ± 0.15; (turn down 1:1) % of span |
| Long-term stability | < ± 0.1; (turn down 1:1; per year) % of span |
| Temperature coefficient zero point | < ± 0.2; (0...200 °C) % of span / 10 K |
| Temperature coefficient range | < ± 0.15; (0...200 °C) % of span / 10 K |
| Approvals / tests |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Shock resistance | DIN EN 60068-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6 / 20 g (10...2000 Hz) |
| MTTF | 149 years |
| Note on approval | Free 6-point calibration certificate included. |
| Displays / controls |
| Indication | Display unit / LED, green; Switching state / LED, yellow; Function indicator / alphanumeric display, 4-digit; Measured values / alphanumeric display, 4-digit |
| Display unit | bar; psi; kPa; % of span |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Operating voltage | 20...32 DC V |
| Electricity consumption | 3,6...21 mA |
| Standby delay time | 1 s |
| Reverse polarity protection | |
| Integrated watchdog | |
| Environmental conditions |
| Ambient temperature | -25...80 °C |
| Note on ambient temperature | Medium temperature: ≤ 160 °C |
| Storage temperature | -25...100 °C |
| Degree of protection | IP 67; IP 68; IP 69K |
| Field of application |
| Special feature | Gold-plated contacts |
| Application | Flush-mounted for food and beverage industry |
| Media | Paste and solid-containing media; Liquid and gaseous media |
| Medium temperature | -20...200; (-20...90 < 0 bar) °C |
| Min. bursting pressure | 50 bar / 725 psi / 5000 kPa |
| Compressive strength | 30 bar / 435 psi / 3000 kPa |
| Pressure type | Relative pressure; vacuum |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.0 |
| SDCI standard | IO-Link Communication Specification, Version 1.0, January 2009, Folder No: 10.002 |
| Required master port class | A |
| Analog process data | 1 |
| Process data binary | 2 |
| Min. process cycle time | 2,3 ms |
| Supported DeviceIDs | Operating mode / DeviceID; default / 158 |
| SIO mode | |
| Measurement / adjustment range |
| Switching point SP | -0.99...4 bar / -14.35...58 psi / -99...400 kPa |
| Reverse switch point rP | -1...3.99 bar / -14.5...57.85 psi / -100...399 kPa |
| Analog start point | -1...3 bar / -14.5...43.5 psi / -100...300 kPa |
| Analog endpoint | 0...4 bar / 0...58 psi / 0...400 kPa |
| In steps of | 0.005 bar / 0.05 psi / 0.5 kPa |
| Factory setting | SP1 = 1,000 bar / rP1 = 0,920 bar; SP2 = 3,000 bar / rP2 = 2,920 bar; ASP = 0,000 bar / AEP = 4,000 bar |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 50 / L = 163 mm |
| Materials | 1.4404 (stainless steel / 316L); 1.4435 (stainless steel / 316L); PBT; PEI; PFA |
| Materials in contact with the medium | 1.4435 (stainless steel / 316L) |
| Min. pressure cycles | 10 million |
| Suitable for process connection standard | DIN 32676 Series A (DIN) / Clamp DN50; DIN 32676 Series C (ASME BPE) / Clamp 2"; ISO 2852 / Clamp DN51 |
| Surface roughness Ra/Rz of medium-contacting surfaces | Ra < 0,38 µm |
| Fluid for pressure transmission | NEOBEE (food-safe, FDA compliant) |
| Diaphragm diameter | 47,5 mm |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Switching signal; analog signal; IO-Link; (configurable) |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Number of analogue outputs | 1 |
| Analog output current | 4...20, reversible; (scalable) mA |
| Short-circuit protection type | timed |
| Max. load | 300 Ω |
| Max. voltage drop switching output DC | 2 V |
| Continuous current rating of switching output DC | 250 mA |
| Switching frequency DC | 125 Hz |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2; Number of analog outputs: 1 |
| Measuring range | -1...4 bar / -14.5...58 psi / -100...400 kPa |
| Process connection | Clamp DN50 (2") DIN 32676 (ISO 2852) |
| Response times |
| Process value damping dAP | 0...30 s |
| Attenuation analog output dAA | 0,01...99,99 s |
| Step response time analog output | 45 ms |
| Min. response time relay output dAP | 3 ms |
Elektronischer Drucksensor, -1...4 bar, -14,5...58 psi, -100...400 kpa, Clamp DN50 (2'), Schaltsignal, Analogsignal, IO-Link, 4...20, invertierbar, (skalierbar) mA, Steckverbindung, -20...200, (-20...90 < 0 bar) °C, IP 67, IP 68, IP 69K, Relativdruck, Vakuum