| Accuracy / Deviations |
| Repeatability | < 0.1; (with temperature variations < 10 K) % of span |
| Characteristic deviation | < ± 0.25 (BFSL) / < ± 0.5 (LS); (BFSL = Best Fit Straight Line (minimum setting); LS = end-point setting) % of span |
| Long-term stability | < ± 0.05; (per 6 months) % of span |
| Temperature coefficient zero point | < ± 0.2; (0...80 °C) % of span / 10 K |
| Temperature coefficient range | < ± 0.2; (0...80 °C) % of span / 10 K |
| Approvals / tests |
| EMC | EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 radiated HF / 30 V/m; EN 61000-4-4 burst / 2 kV; EN 61000-4-6 conducted HF / 10 V; electromagnetic emission / according to vehicle directive 2004/104/EC; CISPR 25; electromagnetic immunity / according to vehicle directive 2004/104/EC; ISO 11452-2 radiated HF / 100 V/m; ISO 7637-2 pulse / severity level 4 |
| Shock resistance | DIN EN 60068-2-27 / 50 g (11 ms); DIN EN 61373 / Category 3 |
| Vibration resistance | DIN EN 60068-2-6 / 20 g (10...2000 Hz); DIN EN 61373 / Category 2 |
| MTTF | 506 years |
| Printer directive | Good engineering practice; suitable for fluids of group 2; fluids of group 1 on request |
| Railway applications | DIN EN 50155 / IEC 60571 / Class T3, C1, S1 |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 9,6...32 DC V |
| Minimum insulation resistance | 100; (500 V DC) MΩ |
| Protection class | III |
| Reverse polarity protection | |
| Environmental conditions |
| Ambient temperature | -25...80 °C |
| Storage temperature | -40...100 °C |
| Degree of protection | IP 65 |
| Field of application |
| Special feature | Gold-plated contacts |
| Application | For industrial use; For railway applications |
| Media | Liquid and gaseous media |
| Medium temperature | -25...90; (on request: -40...90 °C) °C |
| Min. bursting pressure | 30 bar / 435 psi / 3 MPa |
| Compressive strength | 10 bar / 145 psi / 1 MPa |
| Pressure type | Relative pressure; vacuum |
| Mechanical data |
| Housing | Cylindrical |
| Dimensions | Ø 30 / L = 79,5 mm |
| Materials | 1.4404 (Stainless steel / 316L); FKM; PA; EPDM/X |
| Materials in contact with the medium | 1.4305 (stainless steel / 303); ceramic; seal: FKM DIN 3869-14 |
| Min. pressure cycles | 100 million |
| Choke element present | no (retrofit available) |
| Outputs |
| Total number of outputs | 1 |
| Output signal | Analog signal |
| Number of analogue outputs | 1 |
| Analog output current | 4...20 mA |
| Max. load | 720; (Ub = 24 V; (Ub - 9,6 V) / 20 mA) Ω |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of analog outputs: 1 |
| Measuring range | -1...1 bar / -1000...1000 mbar / -14.5...14.5 psi / -100...100 kPa |
| Process connection | Threaded connection G 1/4 male thread; Internal thread: M5 |
| Response times |
| Step response time analog output | 3 ms |
Electronic pressure sensor, DC, e1 compliant, Connector, Analogue output
Application: Type of pressure: relative pressure , Liquids and gases
Process connection: G ¼ A / M5 I
Operating voltage: 9.6...32 V DC
Electrical design: DC
Output function: 4...20 mA
Measuring range: -1...1 bar
Pressure rating: 10 bar
Bursting pressure min.: 30 bar
Characteristics deviation : < ± 0.25 (BFSL) / < ± 0.5 (LS)
Connection: M12 connector
Housing materials: stainless steel 316L / 1.4404; FPM (Viton); PA; EPDM/X (Santoprene)
Materials (wetted parts): stainless steel (303S22); ceramics; sealing: FPM (Viton); according to DIN 3869-14
Medium temperature: -25...90 * °C
Ambient temperature: -25...80 °C
Protection: IP 65
Accessories (to be ordered separately): Socket, Mounting accessories
Type: PA3509