II 1G Ex ia IIB T6 Ga Ta -20...70°C; II 1G Ex ia IIB T5 Ga Ta -20...80°C; II 2G Ex ia IIC T6 Gb Ta -20...70°C; II 2G Ex ia IIC T5 Gb Ta -20...80°C; II 1D Ex ia IIIC T200 90°C Da Ta: -20...70°C; II 1D Ex ia IIIC T200 100°C Da Ta: -20...80°C
EMC
EN 60947-5-6
Shock and vibration stress
30 g (11 ms) / 10-55 Hz (1 mm)
MTTF
4697 years
Detection range
Real switching distance Sr
10 ± 10 % mm
Electrical connection
Cable
2 m, PVC; 2 x 0.5 mm²
Electrical data
Switching amplifier
Connection to certified intrinsically safe circuits with maximum values: U = 15 V / I = 50 mA / P = 120 mW
Nominal voltage DC
8,2; (1kΩ) V
Supply voltage DC
7.5...30; (when used outside Ex area) V
Electricity consumption
< 1; (blocking; conducting: > 2.1) mA
Protection class
II
Connection to switching amplifier
Environmental conditions
Ambient temperature
-20...80 °C
Degree of protection
IP 67
Field of application
Application
For applications in hazardous explosive areas
Mechanical data
Mounting type
Flush-mountable
Thread designation
M30 x 1.5
Materials
Housing: PBT
Outputs
Continuous current rating of switching output DC
30; (when used outside Ex area) mA
Switching frequency DC
450 Hz
Product features
Electrical version
NAMUR
Output function
Breaker contact
Switching distance
10 mm
Housing
Threaded design
Dimensions
M30 x 1,5 / L = 41 mm
Safety ratings
Max. self-capacitance
145 nF
Max. self-inductance
140 µH
Induktiver Sensor, M30 x 1,5 / L = 41 mm, Schaltabstand 10 mm bündig einbaubar, Öffner, DC, NAMUR, 2 m PVC-Kabel, IP 67, 2-Leiter, Umgebungstemperatur -20...80 °C, Schaltfrequenz 450 Hz