II 1G Ex ia IIC T6 Ga; II 1D Ex ia IIIC T200 90°C Da
EMC
EN 60947-5-6
Shock and vibration stress
30 g (11 ms) / 10-55 Hz (1 mm)
MTTF
3387 years
Detection range
Real switching distance Sr
8 ± 10 % mm
Working distance
0...6,48 mm
Displays / controls
Indication
Switching state / 4 x 90° LED, yellow
Electrical connection - Plug
Plug connection
1 x M12; coding: A; contacts: 4
Electrical data
Switching amplifier
Connection to certified intrinsically safe circuits with maximum values: U = 15 V / I = 50 mA / P = 120 mW
Nominal voltage DC
8,2; (1kΩ) V
Supply voltage DC
7.5...30; (when used outside Ex area) V
Electricity consumption
< 1; (blocking; conducting: > 2.1) mA
Protection class
II
Connection to switching amplifier
Environmental conditions
Ambient temperature
-20...70 °C
Degree of protection
IP 66; IP 67
Field of application
Application
For applications in hazardous explosive areas
Mechanical data
Mounting type
Flush-mountable
Thread designation
M18 x 1
Materials
Housing: special-coated brass; active surface: PBT; LED window: PA
Outputs
Continuous current rating of switching output DC
30; (when used outside Ex area) mA
Switching frequency DC
400 Hz
Product features
Electrical version
NAMUR
Output function
Breaker contact
Switching distance
8 mm
Housing
Threaded design
Dimensions
M18 x 1 / L = 46 mm
Safety ratings
Max. self-capacitance
200 nF
Max. self-inductance
190 µH
Inductive sensor, Metal thread, M18 x 1, Connection to certified intrinsically safe circuits with the max. values U = 15 V / I = 50 mA / P = 120 mW, ATEX approval, Group II, category 1G/2G, Group II, category 1D, Connector, Sensing range 8 mm [f]
Nominal voltage: 8.2 DC; (1kΩ) V
Electrical design: Connection to certified intrinsically safe circuits with the max. values U = 15 V / I = 50 mA / P = 120 mW
Output function: Normally closed
Current rating: < 30; when used outside the hazardous area mA
Length: 46 mm
Mounting: flush mountable
Sensing range: 8 mm
Switching frequency: 400 Hz
Connection: M12 connector
Housing materials: Brass special coating; active face: PBT; connector: PA
Ambient temperature: -20...70 °C
Protection: IP 67
Output status indication: LED yellow (4 x 90°)
Marking of the unit: ExII 1G Ex ia IIC T6 Ga ExII 1D Ex ia IIIC T 90°C Da
Accessories (to be ordered separately): Socket, Mounting accessories