BVS 03 ATEX E 131 X; BVS 04 ATEX E 153 X; IECEx BVS 06.0003X
ATEX equipment marking
II 2G Ex ia IIC T6 Gb Ta -20...70°C; II 2G Ex ia IIC T5 Gb Ta -20...80°C; II 1D Ex ia IIIB T200 90°C Da Ta: -20...70°C; II 1D Ex ia IIIB T200 100°C Da Ta: -20...80°C
EMC
EN 60947-5-6
Shock and vibration stress
30 g (11 ms) / 10-55 Hz (1 mm)
MTTF
1232 years
Detection range
Real switching distance Sr
4 ± 10 % mm
Displays / controls
Indication
Switching state / 2 x LED, yellow
Electrical connection - Socket
Plug connection
1 x M12; coding: A; contacts: 2
Electrical data
Switching amplifier
Connection to certified intrinsically safe circuits with maximum values: U = 15 V / I = 50 mA / P = 120 mW
Nominal voltage DC
8,2; (1kΩ) V
Electricity consumption
< 1; (blocking; conducting: > 2.2) mA
Protection class
III
Connection to switching amplifier
Environmental conditions
Ambient temperature
-20...70 °C
Degree of protection
IP 67
Field of application
Application
position sensor for swivel drives; actuator control; for standard actuators with standard mounting according to ISO 5211 (VDI/VDE)
Mechanical data
Mounting type
not flush-mountable
Materials
Housing: PBT; Cover: PC
Outputs
Switching frequency DC
250 Hz
Product features
Electrical version
NAMUR
Output function
2 x Normally closed contact (NC)
Switching distance
4 mm
Housing
rectangular
Dimensions
40 x 26 x 60 mm
Remarks
Remarks
Magnetic valve circuit Ex-i:; connection to certified intrinsically safe circuits with maximum values:; U = 28 V DC / P = 2 W
Safety ratings
Max. self-capacitance
150; (per intrinsically safe circuit) nF
Max. self-inductance
150; (per intrinsically safe circuit) µH
Induktiver Sensor, 40 x 26 x 60 mm, Schaltabstand 4 mm nicht bündig einbaubar, 2 x Öffner, DC, NAMUR, M12 / Rd24 Steckverbindung, IP 67, 3-Leiter, Umgebungstemperatur -20...70 °C, Schaltfrequenz 250 Hz