| Approvals / tests |
| Approval | BVS 08 ATEX E026; IECEx BVS 09.0016 |
| ATEX equipment marking | II 1G Ex ia IIC T4 Ga; II 1D Ex ia IIIC T125°C Da |
| EMC | EN 60947-5-2 |
| MTTF | 2942 years |
| Detection range |
| Submersion depth side | 5...7 mm |
| Electrical connection |
| Cable | 0.5 m; 2 x 0.06 mm², PTFE |
| Electrical data |
| Switching amplifier | Connection to certified intrinsically safe circuits with maximum values: U = 15 V / I = 50 mA / P = 120 mW |
| Nominal voltage DC | 8,2; (1kΩ) V |
| Supply voltage DC | 5...25; (for use outside Ex area) V |
| Electricity consumption | < 1.2; (blocking; conducting: > 2.1) mA |
| Protection class | III |
| Connection to switching amplifier | |
| Environmental conditions |
| Ambient temperature | -40...100 °C |
| Degree of protection | IP 67 |
| Field of application |
| Application | Industrial applications / factory automation |
| Mechanical data |
| Slot width | 2 mm |
| Materials | Housing: PBT |
| Outputs |
| Switching frequency DC | 5000 Hz |
| Product features |
| Electrical version | NAMUR |
| Output function | Breaker contact |
| Housing | rectangular |
| Dimensions | 8 x 15 x 11 mm |
| Safety ratings |
| Max. self-capacitance | 150 nF |
| Max. self-inductance | 120 µH |
Slot sensor, 8 x 15 x 11 mm, normally closed, DC NAMUR, 0.5 m, IP 67, 2-wire, ambient temperature -40...100 °C, switching frequency 5000 Hz