| Accuracy / Deviations |
| Repeatability | ± 5 mm |
| Measurement error | ± 7 mm |
| Offset error | 5 mm |
| Resolution | 1 mm |
| Temperature influence per 10 K | ± 0,2 % |
| Approvals / tests |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 / in closed metal enclosure; DIN EN 61000-6-4 / in plastic or open metal enclosure |
| Shock resistance | DIN EN 60068-2-27 / 50 g (11 ms) / 25 g (6 ms) with reference rod 0.5 m |
| Vibration resistance | DIN EN 60068-2-6 / 5 g (10...2000 Hz) / 1 g (5...200 Hz) with reference bar 0.5 m |
| MTTF | 205 years |
| Displays / controls |
| Indication | Display unit / 3 x LED, green; Switching state / 4 x LED, yellow; Fill level / alphanumeric display, 4-digit; Parameter setting / alphanumeric display, 4-digit |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 7, gold-plated |
| Electrical data |
| Operating voltage | 18...30 DC V |
| Electricity consumption | < 30 mA |
| Protection class | III |
| Standby delay time | < 3 s |
| Measurement principle | Guided microwave |
| Reverse polarity protection | |
| Environmental conditions |
| Ambient temperature | -25...60 °C |
| Storage temperature | -40...85 °C |
| Degree of protection | IP 67 |
| Field of application |
| Special feature | Gold-plated contacts |
| Application | for industrial use |
| Media | liquid media |
| Dielectric constant of medium | ≥ 5 |
| Recommended media | Water; water-based media |
| Not suitable for | See instruction manual, chapter "Intended use". |
| Process temperature | -25...80; (90 < 1 h ; see note under Remarks) °C |
| Compressive strength | 16 bar / 1.6 MPa |
| Vacuum tightness | -1000 mbar / -0.1 MPa |
| MAWP for applications according to CRN | 16 bar |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 CDV |
| Required master port class | A |
| Analog process data | 1 |
| Process data binary | 4 |
| Min. process cycle time | 2,3 ms |
| Supported DeviceIDs | Operating mode / DeviceID; default / 11 |
| SIO mode | |
| Measurement / adjustment range |
| Active area A | L-40 mm |
| Inactive zone I1 / I2 | 30 / 10 mm |
| Measurement frequency | 4 Hz |
| Switching point SP | 15...L-30 mm |
| Reverse switch point rP | 10... L-35 mm |
| In steps of | 5 mm |
| Hysteresis | > 5 mm |
| Mechanical data |
| Materials | 1.4301 (stainless steel / 304); 1.4404 (stainless steel / 316L); FKM; PBT; PC; PEI; TPE-V |
| Materials in contact with the medium | 1.4305 (stainless steel / 303); probe connection: 1.4435 (stainless steel / 316L); PTFE; FKM |
| Outputs |
| Total number of outputs | 4 |
| Output signal | switching signal; IO-Link |
| Electrical version | PNP |
| Number of digital outputs | 4 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2,5 V |
| Continuous current rating of switching output DC | 200 mA |
| Short-circuit protection type | thermal, timed |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 4 |
| Rod length L | 100...1600 mm |
| Process connection | Threaded connection 3/4" NPT male thread |
| Remarks |
| Notes | For high process temperatures: The relevant temperature is at the process connection. The actual medium temperature may be higher. |
Elektronischer Füllstandsensor, PNP, Schaltsignal, IO-Link, Druckfestigkeit 16 bar, 3/4' NPT Außengewinde, Steckverbindung