| Approvals / tests |
| EMC | DIN EN 61000-6-2 / : 2006; DIN EN 61000-6-4 / : 2011 / open enclosures; DIN EN 61000-6-3 / : 2011 / closed enclosures |
| Shock resistance | DIN EN 60068-2-27 / 50 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6 / 20 g (10...2000 Hz) |
| MTTF | 223 years |
| UL approval | Certification number UL / H001 |
| Displays / controls |
| Indication | Switching state / LED, yellow; Operating state / LED, green |
| Electrical connection |
| Plug connection | 1 x M12; Coding: A; Contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 18...30 DC V |
| Electricity consumption | < 50 mA |
| Protection class | III |
| Measurement principle | Capacitive |
| Reverse polarity protection | |
| Environmental conditions |
| Ambient temperature | -20...85 °C |
| Note on ambient temperature | Medium temperature: < 100 °C; -20...60 °C; medium temperature: < 150 °C |
| Storage temperature | -40...85 °C |
| Degree of protection | IP 68; IP 69K |
| Field of application |
| Special feature | Gold-plated contacts |
| Mounting | For installation in existing vibration fork sleeves |
| Media | Liquid and pasty media; powdery media |
| Recommended media | water; water-based media; oils; oil-based media; powdery media |
| Not suitable for | See instruction manual, chapter "Intended use". |
| Probe length | 38 mm |
| Container pressure | -1...40 bar / -0.1...4 MPa |
| Medium temperature | -20...100 °C |
| Medium temperature short-term | -20...150; (1 h) °C |
| Interfaces |
| Communication interface | IO-Link |
| Transmission type | COM2 (38.4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Smart Sensor - SSP 0 / Generic Profiled Sensor; Function / Device identification; Function / Process data variable |
| Required master port class | A |
| Analog process data | 1 |
| Process data binary | 2 |
| Min. process cycle time | 2,3 ms |
| Supported DeviceIDs | Operation mode / DeviceID; default / 370 |
| SIO mode | |
| Mechanical data |
| Dimensions | Ø 30 / L = 125,5 mm |
| Materials | 1.4404 (stainless steel / 316L); PEEK; PEI; FKM |
| Materials in contact with the medium | PEEK surface finish: Ra < 0.8 µm / Rz = 4 µm |
| Outputs |
| Total number of outputs | 2 |
| Output signal | switching signal; IO-Link |
| Electrical version | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | Normally open contact (NO) / Normally closed contact (NC); (configurable) |
| Max. voltage drop switching output DC | 2,5 V |
| Continuous current rating of switching output DC | 100 mA |
| Short-circuit protection type | timed |
| Short-circuit protection | |
| Overload resistant | |
| Product features |
| Number of inputs and outputs | Number of digital outputs: 2 |
| Factory setting | water-based media |
| Process connection | G 1 external thread |
| Response times |
| Response time | < 0,5 s |
Elektronischer Füllstandsensor, PNP/NPN, Schaltsignal, IO-Link, Sondenlänge 38 mm, Mediumtemperatur -20...100 °C, G 1 Außengewinde, Steckverbindung