| Accuracy / Deviations |
| Accuracy | 4; (in range 20...80 % RH) % RH |
| Resolution | 0,1 % RH |
| Approvals / tests |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-4 |
| MTTF | 178 years |
| UL approval | File number UL / E224228 |
| Electrical connection |
| Plug connection | 1 x M12 (EN 61067-2-101); coding: A; contacts: 4, gold-plated |
| Electrical data |
| Operating voltage | 12...30 DC V |
| Protection class | III |
| Standby delay time | < 1 s |
| Measurement principle | Capacitive |
| Reverse polarity protection | |
| Environmental conditions |
| Ambient temperature | -40...70 °C |
| Note on ambient temperature | Ambient humidity: ≤ 90 % RH; non-condensing |
| Storage temperature | -40...85 °C |
| Note on storage temperature | Storage humidity: ≤ 90 % RH; non-condensing |
| Degree of protection | IP 20; (sensor only: IP 57) |
| Field of application |
| Special feature | Gold-plated contacts |
| Measurement / adjustment range |
| Measuring range | 0...100 % RH |
| Mechanical data |
| Mounting method | DIN rail and rear panel mounting; (TH35 (EN 60715) / M5) |
| Dimensions | 140 x 40 x 38 mm |
| Materials | Plastic UL94 V-0; light grey |
| Built-in position | Vertical; connection top |
| Outputs |
| Total number of outputs | 2 |
| Output signal | Analog signal |
| Number of analogue outputs | 2 |
| Analog output current | 4...20 mA |
| Max. load | (Ub - 12 V) / 20 mA Ω |
| Product features |
| Number of inputs and outputs | Number of analogue outputs: 2 |
| Response times |
| Response time | < 30; (T90) s |