EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-6 HF conducted / 10 V; EN 55011 / Class B; EN 60947-5-2
MTTF
1727 years
UL approval
Ta / 0...40 °C; Enclosure type / Type 1; Voltage supply / Hazardous voltage; UL certification number / A047; UL file number / E174191
Embedded software included
Detection range
Real switching distance Sr
20 ± 10 % mm
Working distance
0...16,2 mm
Displays / controls
Indication
Switching state / 1 x LED, yellow
Electrical connection - Plug
Plug connection
1 x M12; coding: A; contacts: 4
Electrical data
Operating voltage
10...36 DC V
Electricity consumption
15; (24 V) mA
Protection class
II
Reverse polarity protected
Environmental conditions
Ambient temperature
-25...80 °C
Degree of protection
IP 67
Mechanical data
Mounting type
not flush-mountable
Materials
Active surface: PPE orange; connection module: PPE black; screw: zinc-plated steel
Outputs
Max. voltage drop switching output DC
2,5 V
Continuous current rating of switching output DC
250 mA
Switching frequency DC
300 Hz
Short-circuit protection type
timed
Short-circuit protection
Overload resistant
Product features
Electrical version
PNP
Output function
Normally open contact (NO) / Normally closed contact (NC); (selectable)
Switching distance
20 mm
Housing
rectangular
Dimensions
40 x 40 x 121 mm
Remarks
Remarks
5 layers of active switching zone selectable; for programming as normally closed contact (NC), disconnect wire bridge.
Inductive sensor, Rectangular, plastics, DC PNP, Connector, Sensing range 20 mm [nf]
Operating voltage: 10...36 V DC
Electrical design: DC PNP
Output function: normally open / closed programmable
Current rating: 250 mA
Mounting: non-flush mountable
Sensing range: 20 mm
Switching frequency: 350 Hz
Connection: M12 connector
Housing materials: PPE
Ambient temperature: -25...80 °C
Protection: IP 67
Output status indication: LED yellow
Accessories (to be ordered separately): Socket, Mounting accessories