EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 RF radiated / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-6 RF conducted / 10 V; EN 55011 / Class B
MTTF
378 years
UL approval
Ta / 0...40 °C; Enclosure type / Type 1; File Number UL / E174191
Detection range
Real switching distance Sr
22 ± 10 % mm
Working distance
0...17,82 mm
Displays / controls
Indication
Switching state / 4 x 90° LED, yellow
Electrical connection - Plug
Plug connection
1 x 1/2"; Coding: C; Contacts: 2, gold-plated
Electrical data
Operating voltage
20...140 AC/DC V
Protection class
II
Max. standby delay time
1000 ms
Reverse polarity protection
Environmental conditions
Ambient temperature
0...100 °C
Degree of protection
IP 68; IP 69K; ("COP")
Field of application
Special feature
Gold-plated contacts
Application
Use in hygiene areas / Regular cleaning processes
Mechanical data
Mounting type
not flush-mountable
Thread designation
M30 x 1.5
Materials
Housing: 1.4404 (stainless steel / 316L); active surface: PEEK
Outputs
Max. voltage drop switching output DC
5,5 V
Max. voltage drop switching output AC
5,5 V
Minimum load current
5 mA
Max. residual current
1 mA
Continuous current rating of switching output AC
80; (200 (...80 °C)) mA
Continuous current rating of switching output DC
80; (200 (...80 °C)) mA
Short-term current rating of switching output
1200; (20ms / 0,5Hz / 80 mA (> 80°C)) mA
Switching frequency AC
25 Hz
Switching frequency DC
100 Hz
Short-circuit protection type
timed
Short-circuit protection
Overload resistant
Product features
Output function
Normally open contact
Switching distance
22 mm
Housing
Threaded design
Dimensions
M30 x 1,5 / L = 70 mm
Induktiver Sensor, M30 x 1,5 / L = 70 mm, Schaltabstand 22 mm nicht bündig einbaubar, Schließer, AC/DC, 1/2' Steckverbindung, IP 68, IP 69K, ('COP'), 2-Leiter, Umgebungstemperatur 0...100 °C, Schaltfrequenz 25 Hz AC / 100 Hz DC