EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 RF radiated / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-6 RF conducted / 10 V; EN 55011 / Class B
MTTF
1675 years
UL approval
Ta / -25...75 °C; Enclosure type / Type 1; Power supply / Limited Voltage/Current; Certification number UL / A002; File number UL / E174191
Embedded software included
Detection range
Real switching distance Sr
15 ± 10 % mm
Working distance
0...12,1 mm
Displays / controls
Indication
Switching state / 1 x LED, yellow
Electrical connection
Cable
2 m, PUR, Ø 4.0 mm; 3 x 0.34 mm²
Electrical data
Operating voltage
10...30 DC V
Electricity consumption
< 10 mA
Protection class
III
Reverse polarity protection
Environmental conditions
Ambient temperature
-25...75 °C
Degree of protection
IP 67
Mechanical data
Mounting type
not flush-mountable
Thread designation
M30 x 1.5
Materials
Housing: brass white bronze-coated; active surface: PBT orange; LED window: PEI; mounting nuts: brass white bronze-coated
Tightening moment
50 Nm
Outputs
Max. voltage drop switching output DC
2,5 V
Continuous current rating of switching output DC
100 mA
Switching frequency DC
200 Hz
Short-circuit protection
Overload resistant
Product features
Electrical version
NPN
Output function
Normally open contact
Switching distance
15 mm
Housing
Threaded design
Dimensions
M30 x 1,5 / L = 60 mm
Inductive sensor, M30 x 1.5 / L = 61 mm, switching distance 15 mm, non-flush mountable, normally open, DC NPN, 2 m PVC cable, IP 67, 3-wire, ambient temperature -25...70 °C, switching frequency 200 Hz