EN 60068-2-14 Na / TA = -40 °C; TB = 85 °C; t1 = 30 min; t2 = < 10 s; 50 cycles
Salt spray test
EN 60068-2-52 Kb / severity level 5 (4 test cycles)
MTTF
1253 years
UL approval
Ta / -25...70 °C; Enclosure type / Type 1; Power supply / Limited Voltage/Current; UL approval number / A052; UL file number / E174191
Detection range
Real switching distance Sr
12 ± 10 % mm
Working distance
0...9,72 mm
Increased switching distance
Displays / controls
Indication
Switching state / 4 x 90° LED, yellow
Electrical connection - Plug
Plug connection
1 x M12; coding: A; contacts: 3, gold-plated
Electrical data
Operating voltage
10...36 DC V
Electricity consumption
< 10 mA
Protection class
II
Reverse polarity protection
Environmental conditions
Ambient temperature
-40...85 °C
Degree of protection
IP 67; IP 69K
Field of application
Special feature
Gold-plated contacts; Increased switching gap
Application
Use in mobile and harsh applications
Mechanical data
Mounting type
not flush-mountable
Thread designation
M18 x 1
Materials
Housing: 1.4404 (stainless steel / 316L); active surface: LCP white; LED window: PEI; mounting nuts: brass white bronze-coated
Tightening moment
50 Nm
Outputs
Max. voltage drop switching output DC
2,5 V
Minimum load current
2; (only in 2-wire operation) mA
Max. residual current
0.5; (only in 2-wire operation) mA
Continuous current rating of switching output DC
100 mA
Switching frequency DC
200 Hz
Short-circuit protection type
timed
Short-circuit protection
Overload resistant
Product features
Electrical version
PNP/NPN
Output function
Breaker contact
Switching distance
12 mm
Housing
Threaded design
Dimensions
M18 x 1 / L = 70 mm
Inductive sensor, M18 x 1 / L = 70 mm, switching distance 12 mm, non-flush mountable, normally closed, DC PNP/NPN, M12 connector, IP 67, IP 69K, 2-wire, 3-wire, ambient temperature -40...85 °C, switching frequency 200 Hz