EN 61000-4-2 ESD / 4 kV CD / 8 kV AD; EN 61000-4-3 RF radiated / 10 V/m; EN 61000-4-4 Burst / 2 kV; EN 61000-4-6 RF conducted / 10 V; EN 55011 / Class B
MTTF
609 years
UL approval
Ta / 0...40 °C; Enclosure type / Type 1; File Number UL / E174191
Detection range
Real switching distance Sr
5 ± 10 % mm
Working distance
0...4,05 mm
Displays / controls
Indication
Switching state / 1 x LED, yellow
Electrical connection
Required fuse rating
Miniature fuse according to IEC60127-2 Sheet 1; ≤ 2 A; fast
Cable
7 m, PVC; 2 x 0.5 mm²
Electrical data
Operating voltage
20...250 AC/DC V
Protection class
II
Reverse polarity protected
Environmental conditions
Ambient temperature
-25...80 °C
Degree of protection
IP 67
Mechanical data
Mounting type
Flush-mountable
Thread designation
M18 x 1
Materials
Enclosure: brass white bronze-coated; active surface: PBT natural; LED window: PBT natural
Tightening moment
23 Nm
Outputs
Max. voltage drop switching output DC
6 V
Max. voltage drop switching output AC
6,5 V
Minimum load current
5 mA
Max. residual current
2,5 (250 V AC) / 1,3 (110 V AC) / 0,8 (24 V DC) mA
Continuous current rating of switching output AC
250; (350 (...50 °C)) mA
Continuous current rating of switching output DC
100 mA
Short-term current rating of switching output
2200; (20 ms / 0,5 Hz) mA
Switching frequency AC
25 Hz
Switching frequency DC
50 Hz
Short-circuit-proof
Overload resistant
Product features
Output function
Normally open contact
Switching distance
5 mm
Housing
Threaded design
Dimensions
M18 x 1 / L = 80 mm
Remarks
Remarks
Recommendation: After a short circuit, check the device for safe operation.
Induktiver Sensor, M18 x 1 / L = 80 mm, Schaltabstand 5 mm bündig einbaubar, Schließer, AC/DC, 7 m PVC-Kabel, IP 67, 2-Leiter, Umgebungstemperatur -25...80 °C, Schaltfrequenz 25 Hz AC / 50 Hz DC